Card installation
1)
Turn the unit off using the interface (KONTROLA 1/4; UPS).
2)
Set safeguards F3 and F4 to OFF.
3)
Turn off safeguards F1, F2, and F5 by opening the fuse casings. This can be
done in any order.
4)
Wait approx. 30 s to fully discharge the internal batteries.
5)
Unscrew the metal cover of the card slot.
6)
Connect the card cable (cable is in the card slot).
7)
Insert the card in the slot.
8)
Screw the cover on the rear panel.
9)
Connect safeguard F1 by closing the casing.
10) Wait 10 seconds at least.
11) Connect safeguard F2 by closing the casing.
12) Connect safeguard F5 by closing the casing.
13) Set safeguards F3 and F4 to ON.
14) Turn the unit on using the interface (KONTROLA 1/4;UPS).