EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
Type 01 2019-06-10 14:36
Technical Assistance, phone: +48 61 6500 400
42
Table 10. J10 terminal pinout
Pin no.
Name
Description
J10-1
UTI_FAIL_NC
A relay informing that there is no mains - normally closed (J10-1
and J10-3). Opening of the relay indicates that there is no mains.
J10-2
UTI_FAIL_NO
A relay informing that there is no mains - normally open (J10-2
and J10-3). Closing of the relay indicates that there is no mains.
J10-3
GND
Common for NO and NC
COMMUNICATION WITH EXTERNAL
MANAGEMENT/CONTROL SYSTEMS
To establish a connection between a PC and the UPS, connect the PC to the UPS
unit's RS232 interface. The USB communication interface and the management card
are optional equipment with which communication can be established.
The UPS can be managed from external systems (PCs, servers) via free of charge
software.
The software can be used to monitor and configure the UPS unit's parameters and to
manage it. Together with the UPS it creates a safe and reliable protection against
mains interruptions, which guarantees that the powered systems can work without
interruptions.
The up-to-date software and the installation procedure are available at
COMMUNICATION THROUGH RS232 OR USB
By standard, an RS232 communication interface is available for the user. The USB
interface is optional (available together with the parallel operation card). To ensure
correct operation with the PC, the software will prompt the user when to connect the
communication cable during the installation process.
CAUTION!
Only one connection can be used at a time.