Instruction Manual MM850341 ed.01a
___________________________________________6____________________________________________
1.1
Specifications
1.1.1
IRtec Rayomatic 20
•
Measuring ranges:
see par 1.2.1 Table A
•
Accuracy:
@ 23°C ±5°C and
ε
=1.0
IRtec Rayomatic 20-100 and 160:
±0.5% of rdg.
IRtec Rayomatic 20-814 :
±1% of rdg. or ±1 °C whichever is greater
•
Repeatability:
IRtec Rayomatic 20-100 and 160:
± 0.25% of the reading
IRtec Rayomatic 20-814 :
± 0.5% of the reading or ±0.5 °C whichever is greater
•
Response time:
IRtec Rayomatic 20-100 and 160:
28 ms (t95)
IRtec Rayomatic 20-814 :
100 ms (t95)
•
Type of detector:
IRtec Rayomatic 20-100:
Silicium
IRtec Rayomatic 20-160:
InGaAs
IRtec Rayomatic 20-814 :
Thermopile
•
Spectral band:
see par 1.2.1 Table A
•
Emissivity:
adjustable with 2 rotative switch from 0.30 to 1.00
•
Working temperature:
from -20 to +60 °C (without cooling)
from 0 to +50 °C (for laser operation)
•
Storage temperature:
from -30 to +70 °C Silicium and InGaAs detectors
from +10 to +60 °C Thermopile
•
Output signal:
4/20 mA 2 wire current loop – max load 700
Ω
•
Temperature stability:
±0.1 °C/°C for the band exc18 to +28°C
•
Target pinpointing:
optional on-board laser aiming system with remote command
•
Environmental rating:
IP65 (NEMA-4)
•
Power supply:
4-20mA loop
: from 12 to 32 Vdc
Laser pinpointing
: 12 to 32 Vdc
•
Dimension / Weight:
ø 45 mm x 200 mm - 0.5 Kg