MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL
Annex A
Page 3
HA250385
Issue 3 Mar 98
A2 TECHNICAL SPECIFICATION (Input board)
General
Termination
Terminal block
Maximum number of inputs
Six.
Input ranges
±
38mV,
±
150mV,
±
1V,
±
10V
Input types
DC Volts, dc millivolts, dc milliamps (with external shunt), thermocouple, 2 / 3-wire resistance temperature detector
(RTD), Ohms, Contact closure (not channel 1) (Minimum contact closure = 500msec)
Input type mix
Freely configurable
Noise rejection (48 to 62 Hz)
Common mode: >130dB (channel - channel and channel - to - ground). Series mode: >60dB.
Maximum common mode voltage
250 Volts continuous
Maximum series mode voltage
45 mV peak at lowest range; 12 Volts peak at highest range.
Isolation (dc to 65 Hz; BS EN61010)
Installation category II; Pollution degree 2
300 V RMS or dc channel - to - channel (double insulation) and channel - to - ground (basic insulation)
Dielectric strength (BS EN61010)
Channel - to ground =1350 Vac; Channel - to - channel = 2300 Vac (both 1 minute type tests).
Insulation resistance
>10 M
Ω
at 500 V dc
Input resistance
>10M
Ω
(38mV, 150mV, 1V); 68K
Ω
on 10V
(always use mA input type for current inputs with shunts
as it corrects for the 68K)
Overvoltage protection
42 V rms (terminal I to terminal V-), 50 V rms (terminal V+ to terminals V- or I)
Sensor break detection
±
57 nA max.
Recognition time
500 msec.
Minimum break resistance
10 M
Ω
DC Input ranges
Shunt/Attenuator
Resistor or voltage divider for terminal board mounting
Additional error due to shunt
0.1% of input
Additional error due to attenuator
0.2% of input
Performance @ 20 ˚C,
±
2˚C
Resistance inputs
Ranges (including lead resistance)
0 to 150
Ω
, 0 to 600
Ω
, 0 to 6k
Ω
Influence of lead resistance
Error = negligible (3-wire);
Mismatch = 1
Ω
/
Ω
(3-wire)
Temperature scale
ITS90
Resolution and accuracy
@ 20 ˚C,
±
2 ˚C
RTD types, ranges and accuracies
Cu10
JPT100
Ni100
Ni120
Pt100
Pt100A
Pt1000
-20 to + 400
-220 to + 630
- 60 to + 250
- 50 to + 170
-200 to + 850
-200 to + 600
-200 to + 850
General Electric Co.
JIS C1604:1989
DIN43760:1987
DIN43760:1987
IEC 751
Eurotherm Recorders SA
IEC 751
RTD Type
Overall range (˚C)
Standard
0.02 ˚C
0.01 ˚C
0.01 ˚C
0.01 ˚C
0.01 ˚C
0.09 ˚C
0.01 ˚C
Linearization
error, max
Range
0 - 150
Ω
0 - 600
Ω
0 - 6K
Ω
Resolution
5m
Ω
22m
Ω
148m
Ω
Maximum Error - at 20˚C
0.045% r 0.141% range
0.045% r 0.069% range
0.049% r 0.032% range
Maximum Temperature Drift
35 ppm of reading/˚C + 36.6 ppm of range/˚C
35 ppm of reading/˚C + 14.6 ppm of range/˚C
35 ppm of reading/˚C + 1.9 ppm of range/˚C
Maximum Error - at 20˚C
0.085% r 0.051% range
0.084% r 0.038% range
0.084% r 0.029% range
0.275% r 0.030% range
Range
±
38mV
±
150mV
±
1 Volt
±
10 Volts
Resolution
1.4
µ
V
5.5
µ
V
37
µ
V
370
µ
V
Maximum Temperature Drift
80 ppm of reading/˚C +18.6 ppm of range/˚C
80 ppm of reading/˚C + 7.8 ppm of range/˚C
80 ppm of reading/˚C + 1.6 ppm of range/˚C
272 ppm of reading/˚C + 3.5 ppm of range/˚C