MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL
Section 4
Page 4 - 7
HA250385
Issue 2 Mar 98
4.2 CONFIGURATION TECHNIQUES
Configuration menus are treated in the same way as operator menus, with the page and enter keys being used to se-
lect a parameter, and the arrow keys being used to edit it. To return to a higher menu level the cancel (x) key is used.
Figure 4.2 below shows the alarm setpoint sub-menus in an attempt to illustrate these techniques.
Figure 4.2 Configuration techniques
Use arrow keys to scroll
through parameter
choices
Use page keys to move
from parameter to
parameter
Type Absolute High
Type Deviation in
Type Deviation out
Type Rate of Ch Rise
Type Rate of Ch Fall
Enable Latched
Enable Trigger
Alarm : Job 1
Threshold 10.00
Hysteresis 0.00
Dwell 0s
Returns to whichever 'enable' is currently selected.
Conf : Channel 1
Channel : Range
Channel : Alarm 1
Channel : Trace
Enable off
Alarm : Setpoint
Type Absolute Low
Enable Unlatched
Reference 10.00
Deviation 1.00
Change 1.00
Per second
Average 1s
Page up and Scroll up keys shown;
Page down and Scroll down keys
reverse the order in which the menu
items appear.
Characters shown underlined flash on and off when available for edit.
If the Edit indicator is lighted, the
Cancel key cancels all changes
made since the last 'Enter'.
If the Edit indicator is not
lighted, the Cancel key returns to
the Alarm:Setpoint page from
anywhere in these sub-menus.