MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL
Section 4
Page 4 - 11
HA250385
Issue 3 Mar 98
4.5 CHANNEL CONFIGURATION
Figure 4.5.1 Channel configuration pages for thermocouple pages
Offset 0.00
Conf: Channel 1
I/P Range Lo 4.00
I/P Range Hi 20.00
I/P type
I/P type mA
Lin Type linear
Scaled
Val Format XXX.XX
Damping None
Scale high 100.00
Scale Units : GPM
Scale low 0.00
Brk Rsp None
Scrolls through T/C, mA (always use mV
type with current shunt input), V, mA,
RTD, Ohms, Dig, Comms (if fitted), Cont1 (if
fitted), Cont2 (if fitted), Test.
Enter low and high input
range values.
Scrolls through Types Linear,B, C, D, E,
G2, J, K, L, N, R, S, T, U, NiNi/mo, MoRe,
Platinel, Cu10, Pt100, Pt100A, JPt100,
Pt1000, Ni100, Ni120, Sqr root,
X^3/2, X^5/2,
Scrolls through decimal
point positions for
displayed value.
Scrolls through: none,
2, 4, 8....128, 256 seconds.
Use arrow
and cursor
keys to
enter
values and
units text
Scrolls through
None, Drive hi(gh),
Drive lo(w).
Use arrow and cursor keys
to enter offset
Channel : Range
Channel : Alarm 1
Channel : Trace
Tag WATER FLOW
Use arrow keys and cursor key
to enter channel name
Choose scaled
or unscaled