The unit's electronic controller acts on the parts of the solar system in relation to several characteristic parameters
and can manage the components necessary for operation of a solar circuit .
The parameters defining management of the solar system are:
Auto-restart management
The AutoStart function allows automatic restart of the unit following a shutdown caused by a power failure .
This function can be enabled or disabled depending on the value associated with the parameter H01
INSTALLATION
Parameter
code
Description of parameter
Default
value
Range of settable values
n01
Probe used as a reference in tank
0
0-low/1-high
n02
Solar pump min . operation time
15 min
1 ~ 30min
n03
Temperature difference between panel and storage
tank to activate pump
5 °C
0 ~ 20 °C
n04
Enabling solar panel forced cooling at night
0
0-No\1-YES
n05
Night forced cooling function start time
0 h
0 ~ 23 h
n06
Night forced cooling function end time
6 h
0 ~ 23 h
n07
Temperature for enabling night forced cooling
70 °C
40 ~ 90 °C
n08
Temperature lowering in night forced cooling
10 °C
1 ~ 40 °C
n09
Panel critical temperature for forced heat dissipation
68 °C
50 ~ 90 °C
n10
Max . storage tank temperature for solar pump forced
shutdown
70 °C
50 ~ 90 °C
n11
Solar pump priority
0
0-no priority / 1-when solar
pump on, compressor off
Parameter code
Description of parameter
Default value
Range of settable values
H01
Auto-restart
1
0-Not active\1-Active