Control command switch terminal 2

Used to switch between terminal control and communication control. If the command source is 
selected as terminal control, the system will be switched to the communication control mode when 
the terminal is active; vice versa.

38

PID integral pause

When the terminal is active, the PID integral adjustment function is paused, but the proportion and 
differential adjustments of PID are still valid.

39

Switch between frequency source 
master setting and preset frequency

When the terminal is active, the frequency source A is replaced by the preset frequency (F0.01)

40

Switch between frequency source 
auxiliary setting and preset frequency

When the terminal is active, the frequency source B is replaced with the preset frequency (F0.01)

43

PID parameter switching

When DI terminal (E2.19 = 1) is used to switch PID parameters, if the terminal is invalid, PID 
parameters use E2.13~E2.15; if the terminal is valid, PID parameters use E2.16~E2.18

44

Custom fault 1

When custom fault 1 and custom fault 2 are active, the inverter respectively alarms fault Err.27 and 
fault Err.28, and deals with them according to the mode selected by the fault protection action 
F8.19.

45

Custom fault 2

47

Emergency parking

If the terminal is valid, the inverter will park at the fastest speed, and the current maintains at the 
set upper limit during the parking process. This function is used to meet the requirements that the 
inverter needs to stop as soon as possible when the system is in a emergency state.

48

External parking terminal 2

In any control mode (Keyboard control, terminal control, communication control), the terminal 
can be used to decelerate the inverter until stop, at the time the deceleration time is fixed for 
deceleration time 4.

49

Deceleration DC braking

If the terminal is valid, firstly the inverter decelerates to the initial frequency of stop DC braking, and 
then switches directly to DC braking status.

50

Clear current running time

If the terminal is valid, the inverter’s current running time is cleared 

Table 1 Multi command functions description:Over 4 segments command terminal, can be combined into 16 states, 
each state corresponds to the 16 instruction set value. As shown in Table 1 below:

K4

K3

K2

K1

Command Setting

Parameters

OFF

OFF

OFF

OFF

0-Stage speed setting 0X

E1.00

OFF

OFF

OFF

ON

1-Stage speed setting 1X

E1.01

OFF

OFF

ON

OFF

2-Stage speed setting 2X

E1.02

OFF

OFF

ON

ON

3-Stage speed setting 3X

E1.03

OFF

ON

OFF

OFF

4-Stage speed setting 4X

E1.04

OFF

ON

OFF

ON

5-Stage speed setting 5X

E1.05

OFF

ON

ON

OFF

6-Stage speed setting 6X

E1.06

OFF

ON

ON

ON

7-Stage speed setting 7X

E1.07

ON

OFF

OFF

OFF

8-Stage speed setting 8X

E1.08

ON

OFF

OFF

ON

9-Stage speed setting 9X

E1.09

ON

OFF

ON

OFF

10-Stage speed setting 10X

E1.10

ON

OFF

ON

ON

11-Stage speed setting 11X

E1.11

ON

ON

OFF

OFF

12-Stage speed setting 12X

E1.12

ON

ON

OFF

ON

13-Stage speed setting 13X

E1.13

ON

ON

ON

OFF

14-Stage speed setting 14X

E1.14

ON

ON

ON

ON

15 Stage speed setting 15X

E1.15

Code

Parameter name

Setting range

Factory setting Change

F1.10

Terminal command mode

0:  Two-wire type 1 1; 

1:  Two-wire type 2 2;

2:  Three-wire type 1;  

3:  Three-wire type 2

0

F1.11

TerminalUP/DOWN

0.001Hz/s~65.535Hz/s

1.000Hz/s

F1.12

Minimum input for AIC1

0.00V~F1.14

0.30V

F1.13

F1.12 corresponding setting

-100.0%~+100.0%

0.0%

F1.14

Maximum input for AIC1

F1.12~+10.00V

10.00V

F1.15

F1.14 corresponding setting

-100.0%~+100.0%

100.0%

F1.25

AIinput setting selection

Units digit:AI1 AI1 Below the minimum input setting selection
0:  Corresponding to the minimum input set 1:0.0%;

000

F1.30

DI filter time

0.000s~1.000s

0.010s

F1.31

AI1 filter time

0.00s~10.00s

0.10s

F1.35

DI terminal Mode slection 1

Units digit:DI1 :
0:  High level active;   1:  Low level active
Tens digit: DI2 (Same as the units digit); 
Hundreds digit: DI3 (Same as the units digit)
Thousands digit: DI4 (Same as the units digit)); 
Ten thousands digit: DI5 (Same as the units digit)

00000

F1.37

DI1 delay time

0.0s~3600.0s

0.0s

F1.38

DI2 delay time

0.0s~3600.0s

0.0s

F1.39

DI3 delay time

0.0s~3600.0s

0.0s

F1.40

Define the input terminal repeat

0: Unrepeatable;
1: Repeatable

0

Содержание JI150

Страница 1: ...www euronormdrives com info euronorm nl 31 0 252 228850 Frequency Drive JI150 Manual...

Страница 2: ...terminals 11 F2 group Output terminal 13 F3 group Start and stop control group 14 F4 group V F control parameter group 15 F5 group Vector control parameter group 15 F6 group Keyboard and display 16 F7...

Страница 3: ...requency inverter The diagrams of these operating instructions are used for convenience of explanation and may be slightly different from the product due to product upgrades Please take this manual to...

Страница 4: ...installation position mm Weight kg L W H A B d E JI150 0R7G4 Z 0 75 138 72 123 5 127 61 5 62 1 1 JI150 1R5G4 Z 1 5 JI150 2R2G4 Z 2 2 JI150 004G4 Z 4 185 72 134 175 45 5 82 1 3 JI150 5R5G4 Z 5 5 0 75 5...

Страница 5: ...ance vector control inverter based on DSP Control method V F control vector control W O PG Automatic torque boost function Realize low frequency 1Hz and large output torque control under the V F contr...

Страница 6: ...trol Jog frequency range 0 00Hz to max frequency jog Ac deceleration time 0 0 6500 0s Built in PID Easy to realize closed loop control system for the process control Automatic voltage regulation AVR A...

Страница 7: ...n At most save three error message and the time type voltage current frequency and work status can be queried when the failure is occurred Key lock and function selection Lock part or all of keys defi...

Страница 8: ...wiring requirements correct selection of accessories such as Voltmeter input power supply etc After completing the wiring please check it correctly and make sure that it is correct before powering it...

Страница 9: ...put status DO output status d0 09 AI1 voltage AI1 input voltage value 0 01V d0 12 Count value Actual pulse count value in counting function d0 13 Length value Actual length in fixed length function d0...

Страница 10: ...nning 0 Running frequency 1 Set frequency 0 F0 11 Command source selection Keyboard control LED off 1 Terminal block control LED on 2 Communications command control LED flashes 3 Keyboard control Comm...

Страница 11: ...rminal 1 The setting of 16 stage speed or 16 kinds of other command can be achieved through the 16 states of the four terminals 13 Multi speed terminal 2 14 Multi speed terminal 3 15 Multi speed termi...

Страница 12: ...then switches directly to DC braking status 50 Clear current running time If the terminal is valid the inverter s current running time is cleared Table 1 Multi command functions description Over 4 se...

Страница 13: ...Ready to run When the inverter main circuit and control circuit power supply has stabilized and the drive does not detect any fault information the drive is in an operational state output ON signal 1...

Страница 14: ...Relay 1 output delay time 0 0s 3600 0s 0 0s F2 15 DO terminal active status selection Units digit Reserve Tens digit Relay 0 Positive 1 Negtive 00000 F2 16 DA1 zero bias coefficient 100 0 100 0 20 0...

Страница 15: ...00 80 F4 11 V F oscillation suppression gain 0 100 0 F4 12 V F separation voltage source 0 9 0 F4 13 V F separation voltage digital setting 0V motor rated voltage 0V F4 14 V F separation voltage rise...

Страница 16: ...F6 06 Inverter module radiator temperature 0 0 100 0 F6 07 Total running time 0h 65535h F6 08 Total power on time 0h 65535h F6 09 Total power consumption 0 65535 F6 10 Product number Inverter product...

Страница 17: ...22 Start protection selection 0 OFF 1 ON 0 F7 23 FDT1 detection value 0 00Hz F0 19 Max frequency 50 00Hz F7 24 FDT1 detection hysteresis value 0 0 100 0 FDT1 level 5 0 F7 25 Frequency reaches detectio...

Страница 18: ...8 12 Automatic fault reset 0 1s 100 0s 1 0s F8 25 Abnormal reserve frequency 60 0 100 0 100 F8 26 Momentary power cut action selection 0 Invalid 1 Deceleration 2 Deceleration and stop 0 F8 28 Recovery...

Страница 19: ...on 1 Compensation mode 1 2 Compensation mode 2 1 Fb 06 Upper limiting frequency for DPWM switching 0 00 15 00Hz 12 00Hz Fb 07 PWM modulation mode 0 Asynchronous 1 Synchronous 0 Fb 08 Random PWM depth...

Страница 20: ...2 stage ac deceleration time selection Same to E1 19 0 E1 24 3 stage running time T3 0 0s h 6500 0s h 0 0s h E1 25 3 stage ac deceleration time selection Same to E1 19 0 E1 26 4 stage running time T4...

Страница 21: ...l gain KP1 0 0 to 200 0 80 0 E2 14 Integration time Ti1 0 01s to 10 00s 0 50s E2 15 Differential time Td1 0 00s to 10 000s 0 000s E2 16 Proportional gain KP2 0 0 to 200 0 20 0 E2 17 Integration time T...

Страница 22: ...rter power 55kW 0 01mH to 655 35mH Inverter power 55kW Motor parameters b0 10 Asynchronous motor no load current 0 01A to b0 03 Inverter power 55kW 0 1A to b0 03 Inverter power 55kW Motor parameters b...

Страница 23: ...back loss when running 40 Fast current limiting timeout 41 Switch motor when running 42 Too large speed deviation 43 Motor overspeed 45 Motor over temperature 51 Initial position error COF communicati...

Страница 24: ...ens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 didn t...

Страница 25: ...he existing problems in the peripheral line 2 replace the drive the power board or contactor 18 Err 18 Current detection fault 1 Check Hall device 2 The drive panel is abnormal 1 Replace the drive pan...

Страница 26: ...___________________________________________________________________ ____________________________________________________________________________________________________________________________________...

Страница 27: ...Hub van Doorneweg 8 2171 KZ Sassenheim NL T 31 0 252 228850 F 31 0 252 228235 E sales euronorm nl I euronormdrives com 27 EURN010000_002_C Delivery program...

Страница 28: ...www euronormdrives com Hub van Doorneweg 8 Sassenheim...

Отзывы: