2
4. Select the Operating Mode from the Programmer’s top row.
5. Select the MNPR™ CT Ratio.
6. If necessary Change Settings using Relay Actual.
III. Basic Programming
A.
Power
Up
Before you can program the MNPR™, you must make sure that the MNPR™ and
Programmer are powered properly. This is accomplished by following these
steps:
1. Apply power to the ETI MNPR™. This can be done in one of three ways:
a. Properly installing the MNPR™ on a network protector.
b. Installing the MNPR™ on a three-phase test set.
c. Connecting the MNPR™ to a 120-volt standard outlet using a MNPR™
Single Phase Power Block cord. A MNPR™ Single Phase Power Block is
a cord that mounts onto the MNPR™ and applies power to one phase of
the MNPR™ input. Because power is being applied to only one phase,
the MNPR™ will scroll
“Network Voltage Too Low To Close”
. This does
not prevent the MNPR™ from being programmed.
2. Connect the Programmer to the MNPR™ using the optical cable.
Make sure the word TOP on the optical connector is facing up.
3. Apply power to the Programmer by plugging the power cable into a standard
120-volt AC outlet. The Programmer will scroll
“MNPR™ Programming Unit
Version XX.XX”
. The MNPR™ will scroll
“Remote Login”
.
B. Programmer CT Ratio
Once the Programmer and MNPR™ are properly powered, the Programmer will
scroll
“Press NEXT to view CT Ratio”
. Pressing the
NEXT
button to display
“800:5”
on the Programmer. Continue to press
NEXT
to select the appropriate
CT ratio.
After you choose the correct CT ratio, press
ENTER
. The Programmer will scroll
“ETI _ _”
. It is from this message or from
“Press A, B, C or D first then 1, 2, 3, or
4 to select an option”
that all other commands are issued.