1. Display Units

 (DU:) - This setting determines whether the Programmer 

displays currents as Milliamps through the MNPR™ or as Amps through the 
network protector bus.  This setting does not affect the operation of the 
MNPR™, and is determined entirely by the preference of the user. 

 

2. Network Voltage

 (NV:) - This variable sets a three-phase average network 

voltage below which, the network protector will not close.  This value is 
usually set to 60 volts.  This feature prevents the network protector from 
closing when there is a severe, low impedance fault on the network.  If the 
MNPR™ sees an average network voltage below this setting, the MNPR™ 
will scroll 

“Network Voltage Too Low to Close”

 

3. Voltage Constant

 (VC:) - This feature allows the user to set the MNPR™ to 

ignore the actual voltage on the network side and operate as if a constant 
voltage of 125-volts was applied to the network side. 

 

4. Odometer Reset

 (OD:) - Pressing 

ENTER

 at this point will reset the MNPR™ 

cycle counter.  The Programmer will ask you to 

“Press Enter to Confirm”

 that 

you want to reset the cycle counter.  Upon pressing 

ENTER

, the programmer 

will proceed to the next variable. 

 

5. Relay Fault

 (FLT:) - This feature allows the user to choose what action the 

MNPR™ will take if it malfunctions.  When the MNPR™ identifies an internal 
error it can either hold its current status or issue and immediate open 
command. 

 

6. Actual Mode

 (ACT:)  - This security feature allows the user to prevent the 

manual alteration of the settings of a MNPR™.  If this variable is changed to 
off, the Relay Actual feature will not operate.  The user will only be able to 
choose from the preset buttons on the top row of the Programmer. 

 

7. Download Mode

 (DWN:) - This security feature only matters when Actual 

Mode is on. It will program the MNPR™ as soon as one of the Relay Actual 
settings is incremented or decremented without the Enter button being 
pressed. 

 

8. ASCII Mode

 (ASC:)  - This feature allows the user to use ASCII protocol to 

program a MNPR™.    If you are interested in utilizing this feature, information 
can be obtained from the factory.  

 

9. Watt-Var

 (WV:) - This variable enables the Watt-Var mode of the MNPR™. 

 

10. Brightness

 (LED:) - This variable controls the brightness of the Programmer 

LED display.  The brightness can range from 0-7. Zero is the brightest. 

 

Содержание MNPR

Страница 1: ...MNPR Programmer Manual IM 7385 002 January 4 2000...

Страница 2: ...dly device Its operation is similar to that of a vending machine Specifically there are letters along the bottom and numbers along the right side of the Programmer face All of the features present on...

Страница 3: ...is being applied to only one phase the MNPR will scroll Network Voltage Too Low To Close This does not prevent the MNPR from being programmed 2 Connect the Programmer to the MNPR using the optical ca...

Страница 4: ...V Displays the version of the MNPR software 5 Mode Displays which of the four MNPR modes is currently active Sensitive standard Time Delay Insensitive or Watt Var 6 Reclose Voltage RV Displays the pre...

Страница 5: ...t Current called the Extended Delay 3 Insensitive Trip Press C 1 the MNPR closes the protector identically to Sensitive and Time Delay Mode The MNPR will open the protector only when the net power flo...

Страница 6: ...nd nothing happens your programmer may be set with the Actual Mode turned off Note Using Relay Actual to program the MNPR settings will not change the programmer s stored settings If the relay is set...

Страница 7: ...ote On 480 volt network protectors the MNPR maybe on the 120 volt side of the potential transformers In this case the display should be multiplied by 2 2 to calculate the actual network voltage B Netw...

Страница 8: ...he ETI_ _ Scroll will cause the MNPR to display Enter Program Password to proceed Because misuse of the Program command can result in damage to the MNPR and the network protector the password is not d...

Страница 9: ...ay XD This variable programs the Extended Delay used in Time Delay Mode and Insensitive Mode When the MNPR senses a trip condition it will wait this amount of time before issuing an open command 9 Ins...

Страница 10: ...want to reset the cycle counter Upon pressing ENTER the programmer will proceed to the next variable 5 Relay Fault FLT This feature allows the user to choose what action the MNPR will take if it malfu...

Страница 11: ...out of order and the Programming Error message appears try resetting the Programmer to see if that clears the error VIII Technical Support The ETI MNPR and Programmer are rugged units meant to be use...

Отзывы: