background image

 

 

4

D.  MNPR™ Operating Modes 

 

The MNPR™ can operate in many different modes.  The top row of the 
Programmer allows you to select the four common operation modes of the 
MNPR™.  Selecting any position of the top row, and pressing 

ENTER

 will revert 

the MNPR™ to preset settings corresponding to each of the four modes. 

 

1. Sensitive

 (standard) - Press 

A, 1

 - This is the most common mode.  The 

MNPR™ will open the protector when reverse net power exceeds the 
Sensitive Trip setting.  It will close the protector when the transformer voltage 
exceeds the network voltage by the Reclose Voltage setting, the phase angle 
of that differential voltage is greater than the Reclose Angle and within the 
close region. 

 

2. Time Delay

 - Press 

B, 1

 - The MNPR™ closes the protector identically to 

Sensitive Mode.  The open process is different.  Once the specified reverse 
net power, the Sensitive Trip, is detected the MNPR™ will wait the Time 
Delay setting before opening the protector.  If, during that period, the absolute 
value of current of any phase exceeds the Instant Current setting, the 
MNPR™ will immediately open the protector.  The user can also program a 
delay for the Instant Current called the Extended Delay. 

 

3. Insensitive Trip

 - Press 

C, 1

 - the MNPR™ closes the protector identically to 

Sensitive and Time Delay Mode.    The MNPR™ will open the protector only 
when the net power flow of the sensitive mode is met and the absolute value 
of the current of any phase exceeds the Insensitive Trip Current setting. The 
user can also program a delay for the Insensitive Trip Current called the 
Extended Delay. 

 

4. Watt-Var

 - Press 

D, 1

 - the MNPR™ closes the protector identically to the 

other three modes. The MNPR™ trip region is rotated counter-clockwise to 
ensure that the network protector will open under certain circumstances.  The 
user can program the current at which the MNPR™ will rotate the trip region, 
the Watt-Var Current.  In addition, the user can program the number of 
degrees to shift the MNPR™ trip region the Watt-Var Angle. 

 

E.  Programming the MNPR™ CT Ratio 

 

The CT ratio allows the MNPR™ to properly display network currents during 
operation.  For the MNPR™ to close a General Electric network protector 
properly, it must know the CT ratio of the network protector. 

 

To program the MNPR™ CT Ratio, press 

A, 2

 at the 

“ETI _ _”

 scroll.  The 

Programmer will instruct you to 

“Press NEXT to View CT Ratios”

.  When the 

proper CT Ratio appears on the display, press 

ENTER

 to program the MNPR™.  

To verify CT Ratio on relay use Relay Status. 

Содержание MNPR

Страница 1: ...MNPR Programmer Manual IM 7385 002 January 4 2000...

Страница 2: ...dly device Its operation is similar to that of a vending machine Specifically there are letters along the bottom and numbers along the right side of the Programmer face All of the features present on...

Страница 3: ...is being applied to only one phase the MNPR will scroll Network Voltage Too Low To Close This does not prevent the MNPR from being programmed 2 Connect the Programmer to the MNPR using the optical ca...

Страница 4: ...V Displays the version of the MNPR software 5 Mode Displays which of the four MNPR modes is currently active Sensitive standard Time Delay Insensitive or Watt Var 6 Reclose Voltage RV Displays the pre...

Страница 5: ...t Current called the Extended Delay 3 Insensitive Trip Press C 1 the MNPR closes the protector identically to Sensitive and Time Delay Mode The MNPR will open the protector only when the net power flo...

Страница 6: ...nd nothing happens your programmer may be set with the Actual Mode turned off Note Using Relay Actual to program the MNPR settings will not change the programmer s stored settings If the relay is set...

Страница 7: ...ote On 480 volt network protectors the MNPR maybe on the 120 volt side of the potential transformers In this case the display should be multiplied by 2 2 to calculate the actual network voltage B Netw...

Страница 8: ...he ETI_ _ Scroll will cause the MNPR to display Enter Program Password to proceed Because misuse of the Program command can result in damage to the MNPR and the network protector the password is not d...

Страница 9: ...ay XD This variable programs the Extended Delay used in Time Delay Mode and Insensitive Mode When the MNPR senses a trip condition it will wait this amount of time before issuing an open command 9 Ins...

Страница 10: ...want to reset the cycle counter Upon pressing ENTER the programmer will proceed to the next variable 5 Relay Fault FLT This feature allows the user to choose what action the MNPR will take if it malfu...

Страница 11: ...out of order and the Programming Error message appears try resetting the Programmer to see if that clears the error VIII Technical Support The ETI MNPR and Programmer are rugged units meant to be use...

Отзывы: