7

Once 

B, 4

 is pressed, the Programmer will display the current MNPR™ status 

“BLOCKED”

 or 

“AUTO”

.  Pressing 

NEXT

 will immediately tell the MNPR™ to 

switch to the other status. 

 

Note: If the MNPR™ is removed from the network protector in the Blocked 
state, it will still be Blocked from closing when re-installed. 

 

B. Open Relay

 - press 

A, 4

. This will immediately cause the MNPR™ to issue a 

Open command to the network protector.  Once the open signal is set, the 
MNPR™ will immediately return to normal operation. 

 

Note: If the user wants the MNPR™ to open the protector and not allow it to 
close, it is necessary to use the Block command (see above) before an 
Open Relay command is issued. 

 

VI. Advanced Programming 

 

This manual has discussed every button combination on the Programmer except for 

D, 4 

- the Program command.  This command does not program the MNPR™.  It 

programs the Programmer. 

 

A.  Level 1 Programming 

 

Pressing 

D, 4

 at the 

“ETI_ _”

 Scroll will cause the MNPR™ to display 

“Enter 

Program Password”

 to proceed. Because misuse of the Program command can 

result in damage to the MNPR™ and the network protector, the password is not 
distributed with the Programmer.  The password can be obtained from the 
factory. 

 

NOTE: If you pressed D, 4 and do not have the password, simply press any 
letter on the Programmer 8 times to return to the 

“ETI  _ _”

 scroll. 

 

Entering the correct password allows the user to program the preset variables for 
each of the modes present on the top row of the Programmer.  As usual, 
pressing 

NEXT

 will toggle through individual variables; 

INC

 and 

DEC

 will adjust 

each variable.  It is possible to adjust multiple variables before pressing 

ENTER

 
Setting these variables and pressing 

ENTER

 does not Program the MNPR™.  

Selecting any of the top row from the 

“ETI _ _”

 scroll will program the MNPR™ to 

those settings.  The variables appear in the following order: 

 

1. Reclose Volts

 (RV:) - This variable programs the reclose voltage for all of the 

presets located on the top row Sensitive (standard), Time Delay, Insensitive 
and Watt-Var. 

 

Содержание MNPR

Страница 1: ...MNPR Programmer Manual IM 7385 002 January 4 2000...

Страница 2: ...dly device Its operation is similar to that of a vending machine Specifically there are letters along the bottom and numbers along the right side of the Programmer face All of the features present on...

Страница 3: ...is being applied to only one phase the MNPR will scroll Network Voltage Too Low To Close This does not prevent the MNPR from being programmed 2 Connect the Programmer to the MNPR using the optical ca...

Страница 4: ...V Displays the version of the MNPR software 5 Mode Displays which of the four MNPR modes is currently active Sensitive standard Time Delay Insensitive or Watt Var 6 Reclose Voltage RV Displays the pre...

Страница 5: ...t Current called the Extended Delay 3 Insensitive Trip Press C 1 the MNPR closes the protector identically to Sensitive and Time Delay Mode The MNPR will open the protector only when the net power flo...

Страница 6: ...nd nothing happens your programmer may be set with the Actual Mode turned off Note Using Relay Actual to program the MNPR settings will not change the programmer s stored settings If the relay is set...

Страница 7: ...ote On 480 volt network protectors the MNPR maybe on the 120 volt side of the potential transformers In this case the display should be multiplied by 2 2 to calculate the actual network voltage B Netw...

Страница 8: ...he ETI_ _ Scroll will cause the MNPR to display Enter Program Password to proceed Because misuse of the Program command can result in damage to the MNPR and the network protector the password is not d...

Страница 9: ...ay XD This variable programs the Extended Delay used in Time Delay Mode and Insensitive Mode When the MNPR senses a trip condition it will wait this amount of time before issuing an open command 9 Ins...

Страница 10: ...want to reset the cycle counter Upon pressing ENTER the programmer will proceed to the next variable 5 Relay Fault FLT This feature allows the user to choose what action the MNPR will take if it malfu...

Страница 11: ...out of order and the Programming Error message appears try resetting the Programmer to see if that clears the error VIII Technical Support The ETI MNPR and Programmer are rugged units meant to be use...

Отзывы: