46
Power Control Processor Configuration Manual
Timed event
A timed event is based on a specific time of day. This example describes how to turn on lights at 7:00
a.m. and then turn off lights at 5:00 p.m.
1:
Within the Arch Setup menu, select the Timeclock menu, and make sure Timeclock is set to
“Enabled”.
2:
Press [Down] to advance to the Schedule Events option.
3:
Press [Enter]
and advance to the “Event Number” selection. Use the numeric keypad or the
[Up]
or
[Down]
buttons to enter the event number. For this example, the event number is
“2”.
4:
Press [Enter]
to commit the selection.
5:
Press [Down]
to navigate to Action. The options for this line include
Preset
,
Sequence
, and
None
. For this example select
Preset
.
6:
Press [Enter] to commit the selection.
7:
Using the same menu selection techniques, set the
options shown to the right.
To activate the timed event:
1:
Navigate to the Arch Control menu.
2:
Select the Presets menu.
3:
Scroll to Preset # and select the event preset number,
(in this example we use #2).
4:
Scroll down one more line to Activate and press [Enter]
.
Your Timed Event will now activate preset #1 every Monday at 5:00 p.m. until manually modified.
See
for the full menu flow.
Holiday shut-off
A holiday shut-off is programmed to temporarily deactivate all presets and sequences set to run during
normal operation. A Holiday Shut-off can be programmed to run for 1–7 days.
1:
Navigate to the Arch Control menu.
2:
Select the Start Holiday Shut-off option.
3:
Navigate to Shut-Off for: line at the bottom of the screen.
4:
Use the [Up]
or
[Down] buttons to select either a 24 or 48 hour run time.
5:
Press [Enter]
.
6:
press the [Up] to navigate to the Start Holiday Shut-Off command.
7:
Press [Enter]
.
The following screen will appear asking you to confirm the start of
the Holiday Shut-off.
• Pushing [Enter]
will start the Holiday Shut-off before the
five minute countdown is completed.
• Pushing [Back] (<) will cancel the Holiday Shut-off.
Schedule Events
Event Number:
2
Action: Preset
Space: 1
Preset: 1
Recurrence: Monday
When: Time
of
Day
Time: 5:00pm
Holiday Shut-Off
begins in 5:00
When this time
expires Scheduled
Events will be
overridden.
[Push Enter to start]
[Push Back to cancel]