Menu and Configuration
13
• Lines 4 displays the rack status. The options in the chart below that are marked “illuminate error
LED” will trigger the red error LED to be lit. The options that are marked as “cycle with others”
share the display by cycling through each applicable message at a rate of one every two seconds.
• Line 5 shows the lowest configured DMX Start address value in the Power Control Processor. If
the panel is patched straight (one for one) the equals sign (=) is used. When the panel is set up
with a custom address, approximate equals sign (
) is used instead.
• Line 6 alternates each second between the status of the DMX connection and, when the ports
are enabled, the status of the sACN connection.
- DMX Input will be displayed as either
Active
,
Inactive
or
Disabled
.
- sACN Input will be displayed as either
Active
,
Inactive
or
Disabled, but only when the ACN
option card is installed
.
• Line 7 shows the status of the built-in Echo station power supply (On or Off) and the current
Power Control Processor software version number.
Status Message
Cause
Illuminate
Error LED?
Cycle With
Others?
System OK
No other messages active
No
N/A
Emergency Active
Emergency look is active
Yes
No
Breakers Tripped***
No voltage detected at one or more relays
Yes
Yes
Relay Mismatch**
One or more relays in the rack are mismatched
Yes
Yes
Relay Removed**
One or more relays in the rack are not found
Yes
Yes
Breaker Mismatch*
One or more breakers don’t match the
configuration
Yes
Yes
Breaker Removed*
One or more breakers in the rack are missing
Yes
Yes
Drive 1/2 Error*
Unable to communicate to breaker drive board
Yes
Yes
Timed Event Hold
User has applied a timed event hold
No
Yes
Holiday Shut-off
User has activated holiday Shut-off
No
Yes
Breaker Error*
Breaker has repeatedly tried and failed to operate
Yes
Yes
Dim Overtemp**
Dimmer is in an overtemp state
Yes
Yes
Invalid Cfg Loaded
User has loaded a configuration file which is
invalid
Yes
Yes
* Sensor IQ panel only
** Echo Relay Panel Mains Feed only
*** Applies to all panels except Echo Relay Panel Feedthrough
For more information on status messages, see
.
Note:
When an Emergency Status is active, no other status indicators will be shown.
Emergency Status will always take precedence over all other status options.