DESCRIPTION OF APPLICATIONS
9.2 Light channel function
Options:
Switching:
ON/OFF to a defined threshold.
Controlling:
ON/light control to a defined set value/(OFF) constant light control.
Regulating:
Light is regulated via linear correlation between the dim value and
the light value.
Default setting: Switching
9.3 Light channel switch-off delay time
• Light channel switch-off delay time
Options: 0 seconds, 30 seconds – 12 hours
Default setting: 5 minutes
9.4 Processing actuator feedback
Objects 16 and 17 (or object 16 when “controlling” or “regulating” is selected)
can be used to evaluate the status object of an actuator. In the event that the
actuator is not only controlled by the detector, the light channel switches to
standby mode if the status of the channel differs from that of the actuator.
9.5 Cyclic sending
The light channel sends its current status in cycles according to specified time
intervals. At the same time, it is also possible to determine whether it repeatedly
sends OFF or ON telegrams in cycles.
9.6 Behaviour at switching lock ON or OFF
Options for each include: “No reaction”, “Switch off” or “Switch on” the
light channel.
9.7 Telegram filter
This can be used to prevent OFF or ON telegrams from being sent through
the light channel.
9.8 Lighting controlled regardless of presence
9.9 Lighting controlled/regulated regardless of presence
An ON telegram can be sent via object 7 to initiate light control/regulation
regardless of presence if this function has been enabled in the parameters
(only visible in controlling/regulating operating mode).