GB

OPERATING INSTRUCTIONS

PD-C360i/24 KNX UP 

(EP10427428)

PD-C360i/24 KNX ECO UP (EP10427435)

www.esylux.com 2/13

LIGHT CHANNEL OBJECTS

Object 0: “Input: Lock light channel” (length = 1 bit)

The switching/dimming outputs for the light channel are locked with an ON 

telegram and unlocked with an OFF telegram.

Parameters can be set to determine the status of the light channel after locking 

and unlocking. 

Object 1/2: “Input: Light channel manual ON/OFF” (length = 1 bit)

Note: essential when in semi-automatic mode!

Manual operation is maintained when persons are present until the switch-

off delay time has elapsed if “while presence” is set in the parameters. Light 

measurement is not active if the parameter “With disabled light processing 

during off-period” has been selected. After this, the detector switches to normal 

operating mode. Manual operation has no impact on motion detection. The 

function is transmitted to communication objects 5/6.

Object 3/4: “Input: Light channel manual dimming” (length = 4 bits)

not for version PD-C360i/24 KNX ECO UP

Function: active when constant light control/regulation has been selected!

Input for dim up/dim down KNX touch sensors. Writing on this object manually 

overrides the light channel and the commands are transmitted to the dimming 

actuator via object 7.

Manual operation is maintained when persons are present until the switch-

off delay time has elapsed if “while presence” is set in the parameters. Light 

measurement is not active if “With disabled light processing during off-period” 

has been selected. After this, the detector switches to normal operating mode. 

Manual operation has no impact on motion detection.

Object 5/6: “Input: Light channel manual dim value” (length = 1 byte)

not for version PD-C360i/24 KNX ECO UP

Function: active when constant light control/regulation has been selected!

Input to preset dim values. Writing on this object manually overrides the light 

channel and the values are transmitted to the dimming actuator via objects 

8 and 9.

Manual operation is maintained when persons are present until the switch-

off delay time has elapsed if “while presence” is set in the parameters. Light 

measurement is not active if “With disabled light processing during off-period” 

has been selected. After this, the detector switches to normal operating mode. 

Manual operation has no impact on motion detection.

Object 7: “Input: Light channel control/regulating without presence” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Operating mode: controlling

This object can be used to enable light control without presence.

Operating mode: regulating

This object can be used to enable light regulation without presence. 

Object 8: “Output: Light channel ON/OFF” (length = 1 bit)

If artificial lighting is required (switching threshold 1/set value via parameter) 

and persons are present, the output sends an ON telegram.

If natural light is sufficient and/or no persons are present, an OFF telegram is 

sent once the switch-off delay time has elapsed.

Object 9: “Output: Light channel 2 ON/OFF” (length = 1 bit)

Function: switching - only available with switching function!

If artificial lighting is required (difference between switching threshold 2 and 

switching threshold 1 via parameter) and persons are present, the output 

sends an ON telegram.

If natural light is sufficient and/or no persons are present, an OFF telegram is 

sent once the switch-off delay time has elapsed.

Object 10/11: “Output: Light channel dimming” (length = 4 bits)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

Telegrams can be transmitted to the dimming actuator via this object by 

manually pressing and holding down a touch sensor (object 2). Only active 

when “constant light control/regulation” has been enabled!

Object 12: “Output: Light channel dim value 1” (length = 1 byte)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

If artificial lighting is required and persons are present, the output sends a 

value telegram (1 byte).

If natural light is sufficient (controller to minimum) and/or no persons are 

present, the lighting is set to 0% or the device switches to orientation lighting 

once the switch-off delay time has elapsed. Only active when “constant light 

control/regulation” has been enabled!

Object 13: “Output: Light channel dim value 2” (length = 1 byte)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

If artificial lighting is required and persons are present, the output sends a 

value telegram (1 byte).

If natural light is sufficient (controller to minimum) and/or no persons are 

present, either 0% is sent or the device switches to orientation lighting once 

the switch-off delay time has elapsed.

Option to offset dim value 2 and dim value 1 via parameter. Only active when 

“constant light control/regulation” has been enabled!

Object 14: “Input: Light channel 1 switching threshold” (length = 2 bytes)

(Operating mode: switching)

This object can be used to specify the switching threshold (lux) for channel 1 

via telegram. This is only available if “switching threshold via telegram” has 

been selected.

Object 14: “Input: Light channel set value control” (length = 2 bytes)

not for version PD-C360i/24 KNX ECO UP

(Operating mode: controlling)

This object can be used to specify the set value (lux) for light control via telegram. 

This is only available if “switching threshold via telegram” has been selected.

Object 14: “Input: Light channel regulating lower light value” (length = 2 bytes)

not for version PD-C360i/24 KNX ECO UP

(Operating mode: regulating)

This object can be used to specify the lower light value (lux) for light regulation 

via telegram. This is only available if “switching threshold via telegram” has 

been selected.

Object 15: “Input: Light channel 2 switching threshold” (length = 2 bytes)

(Operating mode: switching)

This object can be used to specify the switching threshold (lux) for channel 2 

via telegram. This is only available if “switching threshold via telegram” has 

been selected.

Object 15: “Input: Light channel regulating upper light value” (length = 2 bytes)

not for version PD-C360i/24 KNX ECO UP

(Operating mode: regulating)

This object can be used to specify the upper light value (lux) for light regulation 

via telegram. This is only available if “switching threshold via telegram” has 

been selected.

Содержание EP10427428

Страница 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Страница 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Страница 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Страница 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Страница 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Страница 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Страница 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Страница 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Страница 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Страница 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Страница 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Страница 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Страница 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...