ESYLUX EP10427428 Скачать руководство пользователя страница 3

GB

OPERATING INSTRUCTIONS

PD-C360i/24 KNX UP 

(EP10427428)

PD-C360i/24 KNX ECO UP (EP10427435)

www.esylux.com 3/13

Object 16/17: “Input: Light channel 1/2 actuator feedback” (length = 1 bit)

This object can be used to evaluate the status object of an actuator. In the 

event that the actuator is not only controlled by the detector, the detector will 

be switched on with an ON telegram and then switched off once the switch-off 

delay time has elapsed (provided no further movement is detected). If an OFF 

telegram is sent, the detector will be switched off and will then revert immediately 

to standby mode. This is only available if “actuator feedback” has been enabled.

Object 18: “Input: Toggle light channel orientation light” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

An ON telegram changes the setting from orientation light value 1 to orientation 

light value 2, while an OFF telegram switches it from value 2 to value 1.

Object 19: “Input: Light channel orientation light ON/OFF” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

An OFF telegram is used to switch off the orientation light function, while an 

ON telegram switches it on.

Object 20: “Input: Snooze function ON/OFF” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Function: constant light control/regulation

If the snooze function is enabled and presence is detected, the detector sends 

a value specified in the parameters instead of controlling/regulating the light.

LIGHT VALUE OBJECTS

Object 21: “Input: Lock sending light value” (length = 1 bit)

An ON telegram locks sending, while an OFF telegram enables sending of the internal 

light value. This is only active if “Behaviour at switching on lock” has been enabled.

Object 22: “Input: External light value” (length = 2 bytes)

This object can be used to mix an external light value with the internal one for 

the actual value for constant light control/regulation.

This is evaluated using multipliers.

Object 23: “Output: Internal light value 1” (length = 2 bytes)

This object can be used to output the internal light value without offset or 

factor values.

Object 24: “Output: Internal light value 2” (length = 2 bytes)

not for version PD-C360i/24 KNX ECO UP

This object can be used to output the internal light value without offset or 

factor values.

Object 25: “Output: Current light value” (length = 2 bytes)

This object can be used to output the light's current actual value.

This takes into account the offset, the internal light value factor and the external 

light value factor and value. This value is used by the light channel and the 

twilight switch to evaluate the light value.

HVAC CHANNEL OBJECTS

Object 26: “Input: Lock HVAC channel” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

The switching output for the HVAC channel is locked with an ON telegram 

and unlocked with an OFF telegram.

Parameters can be set to determine the status of the channel after locking 

and unlocking. 

Object 27: “Input: HVAC channel ON/OFF” (length = 1 bit) 

not for version PD-C360i/24 KNX ECO UP

This object can be used to switch the HVAC channel on or off manually.

Object 28: “Output: HVAC channel ON/OFF” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

If persons are detected, depending on the input delay, an ON telegram is sent.

If no persons are detected, depending on the switch-off delay time, an OFF 

telegram is sent.

Object 29: “Output: HVAC channel dim value” (length = 1 byte)

not for version PD-C360i/24 KNX ECO UP

This communication object can be used to output a parametrisable dim value 

ranging from 0 - 100%.

Object 30 “Output: HVAC channel scene” (length = 1 byte)

not for version PD-C360i/24 KNX ECO UP

Individual scenes (1 of 64) can be called up for switch ON and switch OFF.

MOTION OBJECTS

Object 31: “Input: Slave/Master motion” (length = 1 bit)

Trigger input for parallel connection of Master/Master or input of Slave.

Object 32: “Input: Lock motion detection” (length = 1 bit)

An ON telegram locks the internal motion detection function, while an OFF 

telegram unlocks it again.

Object 33: “Output: Area 1 motion detection” (length = 1 bit)

Output of own PIR motion detection.

Object 34: “Output: Area 2 motion detection” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Output of own PIR motion detection.

Object 35: “Output: Area 3 motion detection” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Output of own PIR motion detection.

Object 36: “Output: Area 4 motion detection” (length = 1 bit)

not for version PD-C360i/24 KNX ECO UP

Output of own PIR motion detection.

1

3

2

4

Содержание EP10427428

Страница 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Страница 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Страница 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Страница 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Страница 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Страница 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Страница 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Страница 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Страница 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Страница 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Страница 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Страница 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Страница 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...

Отзывы: