GB
OPERATING INSTRUCTIONS
PD-C360i/24 KNX UP
(EP10427428)
PD-C360i/24 KNX ECO UP (EP10427435)
www.esylux.com 3/13
Object 16/17: “Input: Light channel 1/2 actuator feedback” (length = 1 bit)
This object can be used to evaluate the status object of an actuator. In the
event that the actuator is not only controlled by the detector, the detector will
be switched on with an ON telegram and then switched off once the switch-off
delay time has elapsed (provided no further movement is detected). If an OFF
telegram is sent, the detector will be switched off and will then revert immediately
to standby mode. This is only available if “actuator feedback” has been enabled.
Object 18: “Input: Toggle light channel orientation light” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Function: constant light control/regulation
An ON telegram changes the setting from orientation light value 1 to orientation
light value 2, while an OFF telegram switches it from value 2 to value 1.
Object 19: “Input: Light channel orientation light ON/OFF” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Function: constant light control/regulation
An OFF telegram is used to switch off the orientation light function, while an
ON telegram switches it on.
Object 20: “Input: Snooze function ON/OFF” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Function: constant light control/regulation
If the snooze function is enabled and presence is detected, the detector sends
a value specified in the parameters instead of controlling/regulating the light.
LIGHT VALUE OBJECTS
Object 21: “Input: Lock sending light value” (length = 1 bit)
An ON telegram locks sending, while an OFF telegram enables sending of the internal
light value. This is only active if “Behaviour at switching on lock” has been enabled.
Object 22: “Input: External light value” (length = 2 bytes)
This object can be used to mix an external light value with the internal one for
the actual value for constant light control/regulation.
This is evaluated using multipliers.
Object 23: “Output: Internal light value 1” (length = 2 bytes)
This object can be used to output the internal light value without offset or
factor values.
Object 24: “Output: Internal light value 2” (length = 2 bytes)
not for version PD-C360i/24 KNX ECO UP
This object can be used to output the internal light value without offset or
factor values.
Object 25: “Output: Current light value” (length = 2 bytes)
This object can be used to output the light's current actual value.
This takes into account the offset, the internal light value factor and the external
light value factor and value. This value is used by the light channel and the
twilight switch to evaluate the light value.
HVAC CHANNEL OBJECTS
Object 26: “Input: Lock HVAC channel” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
The switching output for the HVAC channel is locked with an ON telegram
and unlocked with an OFF telegram.
Parameters can be set to determine the status of the channel after locking
and unlocking.
Object 27: “Input: HVAC channel ON/OFF” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
This object can be used to switch the HVAC channel on or off manually.
Object 28: “Output: HVAC channel ON/OFF” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
If persons are detected, depending on the input delay, an ON telegram is sent.
If no persons are detected, depending on the switch-off delay time, an OFF
telegram is sent.
Object 29: “Output: HVAC channel dim value” (length = 1 byte)
not for version PD-C360i/24 KNX ECO UP
This communication object can be used to output a parametrisable dim value
ranging from 0 - 100%.
Object 30 “Output: HVAC channel scene” (length = 1 byte)
not for version PD-C360i/24 KNX ECO UP
Individual scenes (1 of 64) can be called up for switch ON and switch OFF.
MOTION OBJECTS
Object 31: “Input: Slave/Master motion” (length = 1 bit)
Trigger input for parallel connection of Master/Master or input of Slave.
Object 32: “Input: Lock motion detection” (length = 1 bit)
An ON telegram locks the internal motion detection function, while an OFF
telegram unlocks it again.
Object 33: “Output: Area 1 motion detection” (length = 1 bit)
Output of own PIR motion detection.
Object 34: “Output: Area 2 motion detection” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Output of own PIR motion detection.
Object 35: “Output: Area 3 motion detection” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Output of own PIR motion detection.
Object 36: “Output: Area 4 motion detection” (length = 1 bit)
not for version PD-C360i/24 KNX ECO UP
Output of own PIR motion detection.
1
3
2
4