background image

GB

OPERATING INSTRUCTIONS

PD-C360i/24 KNX UP 

(EP10427428)

PD-C360i/24 KNX ECO UP (EP10427435)

www.esylux.com 1/13

www.esylux.com

OPERATING INSTRUCTIONS

GB

Congratulations on your purchase of this high-quality ESYLUX product. To ensure correct device operation, 
please read these installation/operating instructions carefully and keep them in a safe place for future 
reference.

1 • SAFETY INSTRUCTIONS

  WARNING! Work on electrical systems must be carried out by authorised personnel only, with due 

regard to the applicable installation regulations. Switch off the power supply before installing the 
system. Please observe the installation regulations laid out in the safety measure for separated 
extra-low voltage (SELV).

Use this product only as intended (as described in the user instructions). Do not make any 
changes or alterations as this will render any warrantees null and void. You should check the 
device for damage immediately after unpacking it. If there is any damage, you should not 
install the device under any circumstances.
If you suspect that safe operation of the device cannot be guaranteed, you should turn the 
device off immediately and make sure that it cannot be operated unintentionally.
For correct use of the device, ensure that the UC network (or KNX/EIB) to be connected is 
designed for protection class 3.

  NOTE: this device must not be disposed of as unsorted household waste. Used devices must be 

disposed of correctly. Contact your local town council for more information.

2 • DESCRIPTION

The ESYLUX PD-C360i/24 KNX UP and 24 KNX ECO UP are presence detectors with a 
360° field of detection and integrated bus coupler designed for ceiling mounting. Follow the 
installation instructions provided when installing the device. The detector is able to control 
lighting (“switching” or “constant light control” features).
For additional features, please refer to the 

“Description of applications”

 section of the operating 

instructions. With a range of up to 24 m in diameter, the presence detector is suitable for use 
in offices, classrooms, conference facilities and halls with natural lighting.

The PD-C360i/24 KNX UP / 24 KNX ECO UP is intended to be used in a KNX (EIB), TP bus 
system in conjunction with other KNX components.

If the PD-C360i/24 KNX UP / 24 KNX ECO UP detects that persons are present in its 
field of detection, it transmits controlling telegrams for light outputs, depending on ambient 
brightness, and for HVAC (heating, ventilation and air conditioning) objects.

• Mixed light measurement is suitable for FL, PL, halogen and incandescent lamps.

Certified KNX/EIB training centres provide specialist training on how to plan, install, 
activate, document and use the ETS (Engineering Tool Software) that is required for 
parameter setting.

3 • INSTALLATION / ASSEMBLY / CONNECTION

 

See separate installation instructions.

Mobil-PDi/User

4 • START-UP

All parameter settings are carried out via the ETS 
(Engineering Tool Software). Pressing the programming 
button activates the programming status for the physical 
address on the PD-C360i/24 KNX UP / 24 KNX ECO UP. 
This is indicated by the 

blue LED

.

The product database and application description are 
available to download at www.esylux.com.

5 • SWITCH-ON BEHAVIOUR / LED DISPLAY

• Connect the bus supply

  This initiates a warm-up phase that lasts approx. 10 seconds.
 

The red LED

 and 

green LED

 will slowly flash alternately (f = 1 Hz).

• LED display after warm-up

  Each time motion is detected, this is indicated by 2 flashes of the 

preset LED colour

.

• In the “Master” function, the remote control entries will be acknowledged 

 

by 3 flashes from the 

blue LED.

• 

In the “Slave” function

, each detection is acknowledged by 2 flashes of the 

green LED

.

 

NOTE: The green LED will only light up when motion is detected if it has been enabled by the ETS 
(Engineering Tool Software).

6 • TEST MODE

Parameters can be set via the ETS (Engineering Tool Software).
Test mode switches to the RUN status after “storing”, or 10 minutes after activating the test 
mode. The 

blue LED

 flashes to indicate movement.

7 • REMOTE CONTROL

The optional user remote control Mobil-PDi/User (EM10425547) can be used to regulate/
control the lighting.
The Mobil-PDi/User remote control adjusts the lighting value for the period that persons are 
present plus the switch-off delay time. Thereafter, the values set via the ETS (Engineering Tool 
Software) will apply.

 

NOTE: In the “Slave” function the detector does not respond to the remote control!

The Mobil-PDi/User can be used to control the lighting as follows:
• switching on or off
• dimming (only with “controlling” feature)
• storing and calling up of 2 scenes
• pressing the 

“Reset”

 button resets the KNX presence detector to the 

values set via ETS (Engineering Tool Software). The stored light scenes 
1 + 2 are kept.

For further information, please refer to the operating instructions for 
the Mobil-PDi/User remote control.

8 • ESYLUX MANUFACTURER'S GUARANTEE

ESYLUX products are tested in accordance with applicable regulations and manufactured 
with the utmost care. The guarantor, ESYLUX Deutschland GmbH, Postfach 1840, D-22908 
Ahrensburg, Germany (for Germany) or the relevant ESYLUX distributor in your country (visit 
www.esylux.com for a complete overview) provides a guarantee against manufacturing/
material defects in ESYLUX devices for a period of three years from the date of manufacture.
This guarantee is independent of your legal rights with respect to the seller of the device.
The guarantee does not apply to natural wear and tear, changes/interference caused by 
environmental factors or damage in transit, nor to damage caused as a result of failure to 
follow the user or maintenance instructions and/or as a result of improper installation. Any 
illuminants or batteries supplied with the device are not covered by the guarantee.
The guarantee can only be honoured if the device is sent back with the invoice/receipt, 
unchanged, packed and with sufficient postage to the guarantor, along with a brief 
description of the fault, as soon as a defect has been identified.
If the guarantee claim proves justified, the guarantor will, within a reasonable period, either 
repair the device or replace it. The guarantee does not cover further claims; in particular, 
the guarantor will not be liable for damages resulting from the device's defectiveness. If the 
claim is unfounded (e.g. because the guarantee has expired or the fault is not covered by the 
guarantee), then the guarantor may attempt to repair the device for you for a fee, keeping 
costs to a minimum.

• 

PD-C360i/24 KNX UP

• 

PD-C360i/24 KNX ECO UP

Содержание EP10427428

Страница 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Страница 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Страница 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Страница 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Страница 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Страница 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Страница 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Страница 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Страница 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Страница 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Страница 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Страница 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Страница 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...

Отзывы: