13. LIGHT VALUE

13.1 Current light value

The current light value can be transmitted either in cycles or from a specified 
offset to the last actual value sent. This value is calculated as follows:

Value = [light value from sensor x modifier x multiplier] + offset

Object 21 can be used to lock sending of the current light value. This allows 
you to send either the current value or a value specified in the parameters.

13.2 External light value

An external sensor can also be integrated and assessed via KNX for internal 
light control/regulation. The actual value for controlling/regulating is then:

Value = actual light value + [external light value x modifier x multiplier]

13.3 Internal light value

You can also check light control/regulation by using objects 23 and 24 
to output the internal light value directly from the sensor without factor or 
offset values. This value is always sent along with the current light value via 
communication object 25.

14. ALARM

The alarm function can be set to react differently or the same at switch ON 
and switch OFF.
The alarm output (object 45) can be locked using object 43. Options for 
behaviour at switching lock ON or OFF via object 43 include “no reaction”, 
“switch OFF”, “switch ON”.
The number of detected movements within a time frame can be set.

Содержание EP10427428

Страница 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Страница 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Страница 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Страница 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Страница 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Страница 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Страница 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Страница 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Страница 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Страница 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Страница 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Страница 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Страница 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...

Отзывы: