DESCRIPTION OF APPLICATIONS

1. MASTER/SLAVE

The Master detects presence and evaluates it according to set parameters.

“Lighting ON/OFF” or “lighting light value higher/lower”

The Slave is used exclusively to extend the field of detection. Presence is 
transmitted to the Master (object 31) for evaluation according to the set 
parameters.

• Master/Master selection

Two Masters can work in parallel to extend the field of detection.
Each Master evaluates the presence (object 33) according to its parameters 
set via the ETS (Engineering Tool Software) and regulates/controls the lighting 
appropriately.

Default setting: Master

4. REMOTE CONTROL

This is where you can disable operation via the Mobil-PDi/User or X-REMOTE 
(iPhone).

  Caution: Remote control is disabled in test mode.

2. TEST MODE

(only for Master device configuration)

When test mode is “ON”  

  light measurement is disabled.

When test mode is enabled, the connection with the lighting system is checked.
If the motion sensor detects movement, the lighting will be “ON” for 5 seconds, 
followed by a dead time of 1 second “OFF”.

The blue LED

 indicates that movement has been detected.

Test ON switches to test OFF automatically after 10 minutes, or when the 
parameters are stored.

  Note: During test  

  Slave input enabled.

3. BEHAVIOUR AFTER ETS DOWNLOAD/RESET

Choose from: “No reaction”, “ON”, “OFF”
During the process, the following objects are sent:

Switching operating mode:

- Object 8: “Output: Light channel 1 ON/OFF”
- Object 9: “Output: Light channel 2 ON/OFF”

“Controlling” or “regulating” operating mode:

- Object 8: “Output: Light channel ON/OFF”
- Object 12: “Output: Light channel dim value 1”
- Object 13: “Output: Light channel dim value 2”

- Also, object 28: “Output: HVAC channel ON/OFF”

Содержание EP10427428

Страница 1: ...download at www esylux com 5 SWITCH ON BEHAVIOUR LED DISPLAY Connect the bus supply This initiates a warm up phase that lasts approx 10 seconds The red LED and green LED will slowly flash alternately...

Страница 2: ...tion switching only available with switching function If artificial lighting is required difference between switching threshold 2 and switching threshold 1 via parameter and persons are present the ou...

Страница 3: ...Internal light value 2 length 2 bytes not for version PD C360i 24 KNX ECO UP This object can be used to output the internal light value without offset or factor values Object 25 Output Current light...

Страница 4: ...from 0 100 Object 40 Output Twilight switch scene length 1 byte not for version PD C360i 24 KNX ECO UP Individual scenes 1 of 64 can be called up for switch ON and switch OFF PRESENCE SIMULATION OBJEC...

Страница 5: ...l PDi User or X REMOTE iPhone Caution Remote control is disabled in test mode 2 TEST MODE only for Master device configuration When test mode is ON light measurement is disabled When test mode is enab...

Страница 6: ...he sensors each second to determine whether further motion has been detected object 33 You can use one of the parameters to set the sensor s level of sensitivity Object 32 can be used to lock motion d...

Страница 7: ...operation active during off period is set the detector turns the lighting to 100 during this period Once the off period comes to an end and if there are persons present the device will start controlli...

Страница 8: ...ent that the actuator is not only controlled by the detector the light channel switches to standby mode if the status of the channel differs from that of the actuator 9 5 Cyclic sending The light chan...

Страница 9: ...n binary form objects 8 and 9 as dim values objects 12 and 13 0 100 or as scenes objects 3 4 and 5 6 1 64 Individual parameters can be set for the switch ON and OFF values 10 2 Controlling Dim value w...

Страница 10: ...ofthumb theslowerthelightingresponds thelongerthesteptime 0 5 10seconds Default setting 2 seconds You can specify 2 light values for light regulation using parameters or telegrams communication object...

Страница 11: ...n OFF telegram changes the setting to orientation light value 1 This is only active if the orientation light has been set to ON Default setting 10 Orientation light value 2 Options 0 5 50 up down menu...

Страница 12: ...ains inactive if it is manually switched using communication object 37 until the off period has elapsed at which point it reverts to normal operating mode DESCRIPTION OF APPLICATIONS 11 HVAC CHANNEL N...

Страница 13: ...External light value An external sensor can also be integrated and assessed via KNX for internal light control regulation The actual value for controlling regulating is then Value actual light value e...

Отзывы: