![ESYLUX EP10427428 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/esylux/ep10427428/ep10427428_operating-instructions-manual_2430019005.webp)
GB
OPERATING INSTRUCTIONS
PD-C360i/24 KNX UP
(EP10427428)
PD-C360i/24 KNX ECO UP (EP10427435)
www.esylux.com 5/13
DESCRIPTION OF APPLICATIONS
1. MASTER/SLAVE
The Master detects presence and evaluates it according to set parameters.
“Lighting ON/OFF” or “lighting light value higher/lower”
The Slave is used exclusively to extend the field of detection. Presence is
transmitted to the Master (object 31) for evaluation according to the set
parameters.
• Master/Master selection
Two Masters can work in parallel to extend the field of detection.
Each Master evaluates the presence (object 33) according to its parameters
set via the ETS (Engineering Tool Software) and regulates/controls the lighting
appropriately.
Default setting: Master
4. REMOTE CONTROL
This is where you can disable operation via the Mobil-PDi/User or X-REMOTE
(iPhone).
Caution: Remote control is disabled in test mode.
2. TEST MODE
(only for Master device configuration)
When test mode is “ON”
light measurement is disabled.
When test mode is enabled, the connection with the lighting system is checked.
If the motion sensor detects movement, the lighting will be “ON” for 5 seconds,
followed by a dead time of 1 second “OFF”.
The blue LED
indicates that movement has been detected.
Test ON switches to test OFF automatically after 10 minutes, or when the
parameters are stored.
Note: During test
Slave input enabled.
3. BEHAVIOUR AFTER ETS DOWNLOAD/RESET
Choose from: “No reaction”, “ON”, “OFF”
During the process, the following objects are sent:
Switching operating mode:
- Object 8: “Output: Light channel 1 ON/OFF”
- Object 9: “Output: Light channel 2 ON/OFF”
“Controlling” or “regulating” operating mode:
- Object 8: “Output: Light channel ON/OFF”
- Object 12: “Output: Light channel dim value 1”
- Object 13: “Output: Light channel dim value 2”
- Also, object 28: “Output: HVAC channel ON/OFF”