Programming
CONVERT.EXE Utility Program Template
The
CONVERT.EXE
Utility Program
utilizes a Command Line
Compiler for configuring the LSRA(-C) on IRC-3, LSS, and FCC
systems. The compiler allows you to create a configuration file and
download it to the LSRA(-C). Template examples when using the
CONVERT.EXE
utility program follow:
LSRA application for IRC-3 system
; LSRA source file template for
IRC-3
LSRA application.
; Definition of commands:
;
; MAX NODES
- Must be set to
64
for IRC-3 operation.
; ANNUNCIATION - Must be set to
GLOBAL
for IRC-3 operation.
; EXTERNAL MSG - Must be set to
INACTIVE
for IRC-3 operation.
; FIRE SYSTEM
- Must be set to
IRC-3
for IRC-3 database.
; MSG ROUTE
- Must be set to
ALL
for IRC-3 operations.
; NETWORK CLASS - Communications class. The number of RS485
;
connections as defined by IRC-3 system.
; NETWORK BAUD - The communications baud rate for IRC-3 connection.
; GEO
- Determines display operations for given market.
; PRINTER TYPE
- Local printer selection.
; PRINTER BAUD
- Selects baud rate at which to communicate with
;
serial printer.
; SWITCH MASK
- Selects which switches are active for both switch
;
positions.
; CURRENT ID
- Defines the base address of the LSRA.
; ERROR ACTION
- For IRC-3 applications, this field defines the
;
number of consecutive panel addresses used.
;
This number can be 0100, 0200, 0300 or 0400.
;:::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::
MAX NODES
64
; 01 - 64
ANNUNCIATION
GLOBAL ; LOCAL - GLOBAL
EXTERNAL MSG
INACTIVE ; ACTIVE - INACTIVE
FIRE SYSTEM
IRC-3
; FCC A, FCC B, IRC-3, LSS
MSG ROUTE
ALL
; ALARM, SUPERVISOR, TROUBLE, ALL
NETWORK CLASS B
; A, B
NETWORK BAUD 9600
; 2400, 4800, 9600, 19200
GEO
USA
; USA, CANADA, EUROPE
PRINTER TYPE
NONE
; NONE, FORM, STRIP
PRINTER BAUD
9600
; 2400, 4800, 9600
SWITCH MASK
FF
; [0][0] - [F][F] [ ENABLE ][ DISABLED ]
CURRENT ID
05
; 05 - 63
ERROR ACTION
0400
; 0?00 ?= number of panel addresses.
;
; Message type definitions:
; AA = Alarm SS = Supervisory TT = Trouble XX = Status zone.
;
; 0 1 2 3 4
; 01234567890123456789012345678901234567890
message AA0509 Message associated with output 0509
;
LSRA
Installation, Operation, Maintenance, and Configuration Manual
4.33
firealarmresources.com
Содержание LSRA
Страница 10: ...firealarmresources com ...
Страница 13: ...Introduction LSRA Installation Operation Maintenance and Configuration Manual 1 3 firealarmresources com ...
Страница 14: ...firealarmresources com ...
Страница 36: ...firealarmresources com ...
Страница 82: ...firealarmresources com ...
Страница 86: ...firealarmresources com ...
Страница 92: ...Worksheets 2 LSRA Installation Operation Maintenance and Configuration Manual firealarmresources com ...