Control via PROFINET IO
6.1.14 Get Version (0xB762)
This service can request information about the CANopen-PN.
Therefore a Write service with a parameter "Dummy" has to be called previously.
PROFINET IO Write Service
Index
Parameter Description
Value range
Data type
0xB762
1
Dummy
-
unsigned 8
The service returns the data with the Read service in the following format:
PROFINET IO Read Service
Index
Parameter Description
Value range
Data type
0xB762
1
Vendor-ID
0x0000 0017
unsigned 32
2
Product code
0x2292 1002
unsigned 32
3
Revision number
(CANopen software,
not firmware)
0xXXXX YYZZ
(depending on version,
Version XXXX.YY.ZZ)
unsigned 32
4
Serial number
[0 .. 0xFFFF FFFF]
unsigned 32
5
Gateway class
0x0000 0003
unsigned 32
6
Protocol version
0x0001 0100
unsigned 32
7
Implementation class
0x0004 0000
unsigned 32
6.1.15 Reset Controller (0xB771)
This service restarts the CANopen-Manager in the CANopen-PN.
The parameter is not evaluated. It should only be used in exceptional cases – because additionally
all CANopen slaves are restarted. This will lead to many PROFINET alarms, which might be
possibly not completely processed, e.g. in the TIA portal.
PROFINET IO Write Service
Index
Parameter Description
Value range
Data type
0xB771
1
CANopen Node-ID
0x01..0x7F
unsigned 8
Page 64 of 105
Manual • Doc. No.: C.2921.21 / Rev. 1.6
CANopen-PN