Software Configuration with the GSDML Composer
Communication
Parameter
In this field the COB-ID and the transmission type of the PDO can be
specified.
COB-ID
The CAN-ID of the selected PDO.
In accordance with CiA 306 [4] in the EDS file “$”
may be used as prefix. This is allowed here too, and the
COB-ID is calculated when exported.
No RTR
Remote Transmit Request
Disabled
Here the process data channel, containing the COB-ID
specified above, can be disabled.
Transmission
Type
Equivalent to the
Transmission Type
of the TPDOs as seen
from the CANopen-PN, see
Transmission Type
in chapter
All other parameters do only apply for TPDOs, see chapter 5.9.3
5.9.2.1 Change Mapping Parameter via Buttons
Insert an object in a PDO
With the -button the object selected in the field
Object selection
is inserted in the selected PDO.
Size and granularity will be taken into account.
In the event of a fault the object will not be inserted (without further acknowledgement).
Dummy Objects
Via the context menu of the
PDO selection
dummy objects can be inserted into RPDOs
(types/indices according to CiA 306 , e.g. “Unsigned8” as object Index 5)
Delete an object in a PDO
Clicking the -button deletes the object in the PDO, which is selected in the
PDO selection
.
Move an object in a PDO
A selected object can be positioned in the
PDO selection
with the buttons and .