MAINTENANCE AND DIAGNOSIS OF FAILURES
RINO operator for sliding gates
65
4
SCRAP
The operator, up until the end of its useful life, must
be dismounted at its location by an installer who is
as well qualified as the person who completed the
assembly, observing the same precautions and
safety measures. In this manner possible accidents
and damage to adjacent facilities will be avoided.
}
The operator must be deposited in the appropriate
containers for subsequent recycling, separating and
classifying of the different materials in line with their
nature. NEVER deposit it in domestic rubbish or in landfills
which are not suitably controlled, as this will cause
environmental contamination.
Problem
Cause
Solution
The operator does not work
and no
LED indicator comes on
Main switch SW1 in “OFF”
Place SW1 in “ON”
Power supply voltage absent
Reestablish the power supply
Electronic fuse F2 blown
Replace F2 using another fuse of the same
value and investigate the cause of failure of F2
Transformer or switchboard failed
Call the technical service
The operator does not work when
the key commands are enabled
DL14 lit up, DL8 and DL9 lit up,
DL10 and DL11 off when operating the
key commands
The key commands signal does not
reach the control panel
Check the key command devices and the
connections
The operator does not work when
the key commands are enabled
DL14 lit up, DL8 and DL9 lit up,
DL10 and DL11 light up when pressing
ST1 and ST2 respectively and DL4 and
DL5 light up briefly
Fuse F1 blown
Replace F1 using another fuse of the same
value and investigate the cause of failure of F1
Operator connections
Check connections
Encoder defective
Call the technical service
The operator does not work when
the key commands are enabled
DL1 and DL3 lit up and flashing quickly
STOP contact open (emergency
stop pushbutton enabled or cables
disconnected)
Close STOP contact
The gate does not reach the
stopper
Hard points on the gate run
Move by hand and remove the hard points
Open/close programming incorrect
Carry out the programming correctly
Limit switch magnets incorrectly
positioned
Adjust the limit switch magnets in the gate
Motor sensitivity very high, not
suitable for the weight of the gate
Adjust motor sensitivity using the P.M.
potentiometer
The gate does not reach the
stopper
DL8 off
Opening safety device (photocell o
strip) enabled
Remove any possible obstacles
Fuse F3 blown (photocell without
supply)
Replace F3 using another fuse of the same
value and investigate the cause of failure of F3
The gate opens but does not close
DL9 off
Closing safety device (photocell o
strip) enabled
Remove any possible obstacles
Fuse F3 blown (photocell without
supply)
Replace F3 using another fuse of the same
value and investigate the cause of failure of F3
The gate opens but does not close
DL7 remains off always
Closing limit switch continuously
enabled or deteriorated
Call the technical service
The gate closes but does not open
DL6 remains off always
Opening limit switch continuously
enabled or deteriorated
Call the technical service
The gate does not open
DL1 and DL3 lit up and flashing slowly
Photocell testing error
Check photocells, cabling and programming of
DIP6/DIP9 (see page 57)
Fuse F3 blown (photocells without
supply)
Replace F3 using another fuse of the same
value and investigate the cause of the failure
RINO_EN.book Page 65 Thursday, June 10, 2010 5:21 PM
Содержание RINO
Страница 2: ...RINO book book Page 2 Friday June 11 2010 11 00 AM...
Страница 26: ...Actualizado 4 6 10 22 RINO_ES book Page 22 Friday June 11 2010 9 59 AM...
Страница 70: ...Updated 4 6 10 66 RINO_EN book Page 66 Thursday June 10 2010 5 21 PM...
Страница 115: ...RINO book book Page 17 Friday June 11 2010 11 00 AM...