background image

2400VS SERIES

 

 

Erie Water Treatment Controls – Belgium

 

Page 13

 

Diagnostics level 

 

Besides of all programming parameters, a series of operating parameters can be consulted in the diagnostics level; 
particularly during a service intervention, these parameters can be helpful to identify the cause of a problem. 
 

1.

 

Accessing the Diagnostics level: 

 

Make sure that the control valve is in the service mode. 

 

Press the 

scroll 

 button and hold it for 5 sec until the display shows: 

 

 

 
 

 

Within 10 sec, press the 

down 

 button; the display will show:  

  

 
 

 

You are now in the Diagnostics level; use the 

scroll 

 button to advance through the different diagnostics 

parameters. 

 

2.

 

Exiting the Diagnostics level: 

 

If no button is pressed within a time frame of 5 minutes, the microprocessor will exit the diagnostics level 
end return to the service mode. 

 

Press the 

scroll 

 button until the display shows: 

 

 

 
 

 

Press the

 up 

 button or 

down 

 

button to exit the Diagnostics level. 

 

3.

 

Available diagnostic parameters: 

 

Regen X days ago

: display shows number of days since last regeneration of the unit. 

 

In Srvc

: displays show how many days the unit has been in service. 

 

# of Regens

: display shows the number of regenerations that have taken place since installation. 

 

TotVol

: display shows the total water usage through the unit since installation.              

 

LastRgn@

: display shows the water usage at the moment of the last regeneration. 

 

InstFlow

: display shows the instantaneous flow rate.  

 

AvgVol

: display shows the average daily water usage.  

 

Capacity

: display shows the calculated volume of softened water between regenerations.  

 

Hardness

: display shows the setting of the water hardness.  

 

Rsrv

: display shows the setting of the reserve capacity. 

 

Regen @

: display shows the setting of the time of regeneration. 

 

Override

: display shows the setting of the number of days between regenerations.  

 

Cycle X

: display shows the setting of the length of the corresponding regeneration cycle. 

 

Units

: display shows that control is programmed for Metric units.  

 

MTR

: display shows the setting of the water meter. 

 

Capacity

: display shows that control is programmed for hardness setting. 

 

Regen

: display shows the setting of the regeneration mode.  

 

Valve Type

: display shows the valve type setting. 

 

MP Resets

: display shows the number of resets of the microprocessor (

for factory purpose only

). 

 

Memory Reset

: display shows the number of corrupt memory start-ups (

for factory purpose only

). 

 

EZ

: display shows the software version (

for factory purpose only

). 

 

CapToUse:

 display shows the remaining capacity. 

 
 
 

System Check 

Exit 

Regen XXdays ago 

Содержание 2400VS Series

Страница 1: ...A Division of Aquion Inc 2400VS SERIES Technical Manual...

Страница 2: ...age 10 Diagnostics level Page 13 Parts Replacement Printed Circuit Board Page 14 Drive motor Page 15 Injector Page 15 Backwash flow control Page 16 Brine refill flow control Page 16 Brine tee Page 16...

Страница 3: ...A Division of Aquion Inc Art Nr Tech_Man ENG 2400VS 2013 06...

Страница 4: ......

Страница 5: ...resin The throughput is dependent on the maximum permissible pressure drop for the complete water softener and the maximum permissible specific load of the resin generally taken as 40 litres soft wate...

Страница 6: ...g pressure Operating temperature Electrical rating 1 4 8 3 bar 20 120 psi 2 48 C 35 120 F 24V 50 Hz max 500 mA Regeneration Controller software regeneration initiation regeneration mode time of regene...

Страница 7: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 3 Flow Diagrams SERVICE BACKWASH BRINE SLOW RINSE FAST RINSE BRINE REFILL...

Страница 8: ...1 2 23 2 27 1 70 3 94 3 45 0 68 1 06 2 01 1 63 2 42 2 46 1 97 4 28 4 14 0 68 1 17 2 04 1 78 2 61 2 65 2 20 4 58 The following table is only an indication and is valid for an inlet pressure of 3 bar an...

Страница 9: ...set by increments of 1 min The following tables are only an indication and are valid for a brine valve with a refill rate that equals or exceeds the rate of the refill flow control Brine refill F C Pr...

Страница 10: ...al connections must be done in accordance with local codes Do not install the unit too close to a water heater min 3 m of piping between outlet of unit and inlet of heater water heaters can sometimes...

Страница 11: ...press the scroll button again to switch the motor to full speed which will shorten the transfer time needed by the control valve to reach the next position 9 The motor will move the control valve into...

Страница 12: ...n the correct time of day during a period of several hours consequently in case of prolonged power failure the time of day might not be maintained if this happens the time of day indication will flash...

Страница 13: ...total remaining regeneration time the actual regeneration cycle and the remaining cycle time total remaining actual regen remaining regen time cycle cycle time The control valve can be reset to servic...

Страница 14: ...er access code i e key sequence needs to be entered In the programming modes a flashing indication implicates that this parameter can be adjusted by pressing the up button or down button in this techn...

Страница 15: ...Press the scroll button again the display will show Press the up button or down button to set the volume of resin 5 Press the scroll button again the display will show Press the up button or down butt...

Страница 16: ...ration is started 9 Press the scroll button again the display will show only when the regeneration mode was set to Delayed or Dlyd Immd Press the up button or down button to set the time of regenerati...

Страница 17: ...tions that have taken place since installation TotVol display shows the total water usage through the unit since installation LastRgn display shows the water usage at the moment of the last regenerati...

Страница 18: ...THE WATER PRESSURE Printed Circuit Board 1 Loosen the 3 front cover screws and remove the front cover 2 Disconnect all connectors from the PCB 3 Remove the flat cable of the 3 button control pad from...

Страница 19: ...cover together 3 Lift the valve cover away from the valve body 4 Remove the rotor assembly from the valve cover the white Teflon O ring will remain in the valve cover 5 Remove the seal plate from the...

Страница 20: ...f necessary 6 Install the rotor assembly into the valve body ensuring that the arrow on the worm gear is pointing directly towards the second tooth on the worm drive shaft facing the front of the cont...

Страница 21: ...ing inside of the float valves shaft 6 Install the float valve straight up into the float chamber of the valve body 7 Reverse the procedure for reassembly refer to Parts Replacement Gasket Timer head...

Страница 22: ...nting down mark on the drive shaft pointing up 1 if this is not the case refer to Parts Replacement Drive motor Step 2 Valve body 1 Remove the drain hose from the drain elbow 2 Remove the 6 bolts hold...

Страница 23: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 19...

Страница 24: ...t 12 Leak at riser tube 12 Verify that riser tube is seated correctly and is not cracked Unit fails to regenerate Cause Solution 1 Faulty electrical supply 1 Verify electrical service fuse transfo 2 D...

Страница 25: ...refill flow control 3 Verify that flow control is free of debris Unit uses too much salt Cause Solution 1 Excessive water in brine tank 1 Refer to problem Excessive water in brine tank 2 Unit regener...

Страница 26: ...ributor 2 Verify that distributors are free of debris 3 Crushed lower and or upper distributor 3 Replace distributor s Drain flows continuously Cause Solution 1 Defective PCB 1 Replace PCB 2 Defective...

Страница 27: ...ecked annually 1 Clean out injector 2 Clean brine refill flow control 3 Clean backwash flow control 4 Verify correct functioning of flow meter clean impeller if necessary 5 Verify programming of timer...

Страница 28: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 24 Exploded Views Part Numbers Electronic timer...

Страница 29: ...ief flow meter cable 7 15 222 Screw back plate 2x 8 71502 Screw timer cover 3x 9 70962 Back plate 10 2100 206 Drive shaft 11 15 222 Screw drive motor assy 2x 12 72261 Drive motor 13 568 227 2 Worm 14...

Страница 30: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 26 Valve body...

Страница 31: ...7 L Sleeve mixing valve 25 568 385 2 Brine refill flow control 26 186 118 O ring refill elbow 27 568 336 Refill elbow 28 541 275 Check ball refill elbow 29 413 62 Spring refill elbow 30 21 88 Nut refi...

Страница 32: ...30 24VAC 12VA UK plug J no transfo I Injector 4 1 2 5 B Backwash flow control 0 no flow control Nr Gal min L min E 1 6 6 1 F 1 8 6 8 G 2 0 7 6 H 2 2 8 3 J 2 6 9 8 T 3 0 11 4 K 3 5 13 2 L 4 0 15 1 M 5...

Страница 33: ......

Отзывы: