Procedure
Caution!
Improper handling of batteries can result in the batteries short-circuiting, which
can result in serious injury due to high energy levels. Exercise the necessary
care when working with batteries.
1.
Ensure that the positive (+) cable is disconnected from the external batteries
before following the instruction below.
2.
Remove the bottom cover plate of the DC filter and the cable glands.
3.
Insert and connect the stripped
cables from the external batteries to
the DC filter.
Note:
The figure shows the bottom
of the DC filter.
4.
Position the correct side of the cable clamps for the cross-sectional area of
the cable in accordance with the table below.
Table 2
Cable Clamp Mounting Alternatives
Cable Cross-Sectional Area
Cable Clamp Inscription, Facing
Upwards
95 – 185 mm²
CU 95 – 185
16 – 70 mm²
CU 16 – 70
5.
Tighten the nuts to 7 – 9 Nm torque.
6.
Tighten the cable glands.
13
1/1531-COH 109 2073 Uen H 2006-11-06