4. Troubleshooting (DeviceNet)
4.1.2.6 Uninitialized Network
Master Unit LED
MS NS
Error Description
Light OFF Light OFF Uninitialized network
Absent slave
- Master unit start-up error
- No slave (Error detection before
communication establishment)
- Communications power supply OFF
♦
Process Flowchart
9
No Problem
Check
Check the following:
- Unconnected terminating resistor
- Unconnected or loose connector/signal wire
- Cable disconnection
Finish
No Problem
No Problem
No Problem
Problem exists. (Fix it.)
Problem exists. (Fix it.)
Problem exists. (Fix it.)
Problem exists. (Fix it.)
No problem
No problem
No problem
No problem
Measure voltage of
communications power supply
at the master unit.
Check that power is supplied to all slaves.
Check for master unit configuration.
Replace the master unit.
See 4.1.3.1 and 4.1.3.2.
96
Fieldbus I/O Rev.6
Содержание EM07ZS1647F
Страница 1: ...Rev 6 EM07ZS1647F EPSON RC Option Fieldbus I O ...
Страница 2: ...E PSON RC Option Fieldbus I O Rev 6 ...
Страница 8: ...vi Fieldbus I O Rev 6 ...
Страница 11: ...Table of Contents 5 Maintenance Parts List 151 Appendix A applicomIO Upgrade 153 Fieldbus I O Rev 6 ix ...
Страница 12: ...Table of Contents x Fieldbus I O Rev 6 ...
Страница 80: ...2 Installation 68 Fieldbus I O Rev 6 ...
Страница 88: ...3 Operation 76 Fieldbus I O Rev 6 ...
Страница 164: ...5 Maintenance Parts List 152 Fieldbus I O Rev 6 ...
Страница 168: ...Appendix A applicomIO Upgrade 156 Fieldbus I O Rev 6 ...