8
Parameters
Functions
Settings
Factory
Setting
a
1-12
Decel time 2
0.1 ~ 600 Sec
10.0
a
1-13
JOG Accel time
0.1 ~ 600 Sec
10.0
a
1-14
JOG Decel time
0.0 ~ 600 Sec
10.0
a
1-15 JOG
frequency
1.0Hz~400Hz
6.0
1-16 Auto-accel/decel
0: Linear Accel/Decel
1: Auto accel, linear decel
2: Linear accel, auto decel,
3: Auto Accel/Decel
4: Linear accel. Auto decel, stall prevention
during deceleration
5: Auto accel. Auto decel, stall prevention
during deceleration
0
1-17
S-curve setting in
acceleration
0 ~ 7
0
1-18
S-curve setting in
deceleration
0 ~ 7
0
Group 2: Operation Method Parameters
Parameters
Functions
Settings
Factory
Setting
2-00
Source of frequency
command
0: Digital keypad
1: 0 ~ 10V from AVI
2: 4 ~ 20mA from AVI
3: Controlled by V.R on drive
4: RS-485 communication interface
0
2-01
Source of operation
command
0: By digital keypad
1: By external terminals, keypad STOP
enable
2: By external terminals, keypad STOP
disable
3: By RS-485 communication interface, keypad
STOP enable
4: By RS-485 communication interface, keypad
STOP disable
0
2-02 Stop
method
0: Ramp stop
1: Coast stop
0
2-03 Carrier
freq.
3 ~10K Hz
10
2-04
Reverse operation inhibit 0: Enable reverse
1: Disable reverse
2: Disable forward
0
2-05
ACI (4 ~ 20mA)
input loss detection
0: Decel to 0Hz
1: Stop immediately, display EF
2: Run with the last freq.
0
2-06
Line Start Lockout
0: Enable
1: Disable
0