Standard Specifications 

Voltage Class 

115V 

230V 

Model Number VFD-



L



A/B 

002 004 

002 

004 

007 

015 

Applicable Motor Output (kW) 0.2 0.4  0.2  0.4  0.7 

1.5 

Rated Output Capacity (KVA) 0.6 

1.0 

0.6 

1.0 

1.6 

2.7 

Rated Output Current (A) 

1.6 2.5 

1.6 

2.5 

4.2 

7.0 

Max. Output Voltage (V) 

3-phase corresponds 

to double input 

voltage 

Three-phase corresponds to input voltage 

Output Rating 

Rated Frequency (Hz) 

1.0~400Hz 

Rated Input Current (A) 

9 4.9/1.9 

6.5/2.7 

9.7/5.1 

Ì

/9 

Input voltage Tolerance 

Single phase 

90~132V 50/60Hz 

Single / 3-phase 

180~264V 50/60Hz 

3-phase 

180~264V 

50/60Hz 

Power 

Frequency tolerance 

±

5% 

Control system 

SVPWM (Sinusoidal Pulse Width Modulation, carried frequency 3kHz~10kHz) 

Output Frequency Resolution 

0.1Hz 

Torque Characteristics 

Including the auto-torque, auto-slip compensation, starting torque can be 150% at 

5 Hz 

Overload Endurance 

150% of rated current for 1 minute 

Accel/Decel Time 

0.1~600Sec. (can be set individually) 

V/F pattern 

V/F pattern adjustable 

Control 

Characteristics 

Stall Prevention Level 

20~200%, setting of Rated Current 

Keypad 

Setting by 

▲▼

 keys or V.R 

Frequency 

Setting 

External Signal 

Potentiometer-5K

/0.5W, DC 0 ~ +10V (input impedance 47K

), 4~20mA (output 

impedance 250

), multi-function inputs1 to 3 (3steps, JOG, UP/DOWN 

command), communication setting 

Operation 

Setting 

Keypad 

Setting by RUN//STOP keys 

Signal External 

Signal  M0,M1,M2,M3 can be combined to offer various modes of operation, RS-485 

communication port 

Multi-function Input Signal 

Multi-step selection 0 to 3, Jog, accel/decel inhibit, first/second accel/decel switch, 

counter, PLC Operation, external Base Block (NC,NO) selection  

Operating Characteristics 

Multi-function Output Signal 

AC Drive Operating, Frequency Attained, Non-zero speed, Base Block, Fault 

Indication, Local/Remote indication, PLC Operation indication.  

Other Function 

AVR, S-curve, Over-Voltage Stall Prevention, DC Braking, Fault Records, 

Adjustable Carried Frequency, Starting Frequency Setting of DC Braking , 

Over-Current Stall Prevention, Momentary Power Loss restart, Reverse Inhibition, 

Frequency Limits, Parameter Lock/Reset 

Protection  

Over Voltage, Over Current, Under Voltage, Overload, Electronic thermal, 

Overheating, Self-testing 

Other 

Including EMI Filter 

Cooling  

Forced air-cooling 

Installation Location 

Altitude 1,000 m or below, keep from corrosive gasses, liquid and dust 

Ambient Temperature 

-10

-40

 (Non-Condensing and not frozen) 

Storage Temperature 

-20

 to 60

 

Ambient Humidity 

Below 90%RH (non-condensing) 

Environment  

Vibration 9.80665m/s

2

(1G) less than 20Hz, 5.88m/s

(0.6Gat) 20 to 50Hz 

 

Содержание VFD-L series

Страница 1: ...rive EP ANTRIEBSTECHNIK GmbH Fliederstra e 8 Postfach 1333 63486 Bruchk bel 63480 Bruchk bel Telefon 49 0 6181 9704 0 Telefax 49 0 6181 9704 99 e mail info epa antriebe de www epa antriebe de nderunge...

Страница 2: ...re highly sensitive MOS components on the printed circuit boards These components are especially sensitive to static electricity To avoid damaging these components do not touch the circuit boards with...

Страница 3: ...FD007L21A INPUT 1PH 9 7A 3PH 5 1A 200 240V 50 60Hz OUTPUT 3PH 0 240V 4 2A 1 6kVA 1HP Freq Range 1 0 400Hz MADE IN XXXXX 007L21AT101001 AC Drive Model Input Spec Output Spec Output Freq Range Bar Code...

Страница 4: ...D R E V R U N S T O P P R O G D A T A M O D E R E S E T Do not connect AC power to output WARNING Read the user manual before operation Do not inspect components until LEDs are turned off for at least...

Страница 5: ...rent Motor Multi function indication output contacts Factory default Fault Indication Main circuit power terminals Control circuit terminals Shielded leads If the AC Drive model is VFD002L11A B VFD004...

Страница 6: ...ing knob LED display The signal selection for AVI to input DC0 10V or 4 20 mA U T1 V T2 W T3 R L1 S L2 T L3 Control circuit wiring RA RC 10V AVI M0 M1 M2 M3 GND 120VAC DC28V 3A Relay Wire Gauge 22 24A...

Страница 7: ...s U T1 V T2 and W T3 are connected to the motor terminals U V and W respectively the motor will rotate counterclockwise as viewed from the shaft ends of the motor when a forward operation command is r...

Страница 8: ...alue C 2 Display Process Operation 1 tt 3 Display DC BUS voltage U 4 Display output voltage E 0 a 0 05 User defined coefficient K 0 1 160 1 0 0 06 Software version Read only 0 07 Password input 0 999...

Страница 9: ...Parameters Functions Settings Factory Setting 2 00 Source of frequency command 0 Digital keypad 1 0 10V from AVI 2 4 20mA from AVI 3 Controlled by V R on drive 4 RS 485 communication interface 0 2 01...

Страница 10: ...ters Parameters Functions Settings Factory setting a 4 00 Potentiometer bias freq 0 0 350Hz 0 0 a 4 01 Potentiometer bias polarity 0 positive bias 1 negative bias 0 a 4 02 Potentiometer freq gain 1 20...

Страница 11: ...e program cycle step by step separate by STOP 0 5 04 PLC forward reverse motion 0 15 0 Forward 1 Reverse 0 5 05 Time duration step 0 0 65500 Sec 0 5 06 Time duration step 1 0 65500 Sec 0 5 07 Time dur...

Страница 12: ...exceed during acceleration 10 ocd current exceed during deceleration 11 ocn current exceed during steady state 0 Group 7 Motor Parameters Parameters Functions Settings Factory Setting a 7 00 Motor ra...

Страница 13: ...tion 0 AVR function enable 1 AVR function disable 2 AVR function disable when decel 2 8 16 Dynamic braking voltage 350 450V 380 8 17 DC braking lower bound limit 0 0 400 Hz 0 0 Group 9 Communication P...

Страница 14: ...voltage has exceeded its maximum allowable value 1 Check whether the input voltage falls within the rated AC drive input voltage 2 Check for possible voltage transients 3 Bus over voltage may also be...

Страница 15: ...an not be programmed 1 Switch off power supply 2 Check whether the input voltage falls within the rated AC drive input voltage 3 Switch the AC drive back on Internal memory IC can not be read 1 Check...

Страница 16: ...20mA output impedance 250 multi function inputs1 to 3 3steps JOG UP DOWN command communication setting Operation Setting Keypad Setting by RUN STOP keys Signal External Signal M0 M1 M2 M3 can be combi...

Отзывы: