12
Parameters
Functions
Settings
Factory
Setting
8-05
Max. allowable power loss
time
0.3 ~ 5.0 Sec
2.0
8-06
B.B. time for speed search 0.3~5.0 Sec
0.5
8-07
Max. speed search current
level
30~200% 150
8-08
Skip freq. 1 upper bound
0.0~400 Hz
0.0
8-09
Skip freq. 1 lower bound
0.0~400 Hz
0.0
8-10
Skip freq. 2 upper bound
0.0~400 Hz
0.0
8-11
Skip freq. 2 lower bound
0.0~400 Hz
0.0
8-12
Skip freq. 3 upper bound
0.0~400 Hz
0.0
8-13
Skip freq. 3 lower bound
0.0~400 Hz
0.0
8-14
Auto restart after fault
0~10
0
8-15
AVR function
0: AVR function enable
1: AVR function disable
2: AVR function disable when decel
2
8-16
Dynamic braking voltage
350 ~ 450V
380
8-17
DC braking lower bound limit 0.0 ~ 400 Hz
0.0
Group 9: Communication Parameters
Parameters
Functions
Settings
Factory
Setting
a
9-00
Communication address
1 ~ 247
1
a
9-01
Transmission speed
0: Baud rate 4800
1: Baud rate 9600
2: Baud rate 19200
1
a
9-02
Transmission fault
treatment
0: Warn and continue running
1: Warn and ramp to stop
2: Warn and coasting stop
3: No warn and keep running
0
a
9-03
Modbus communication
watchdog timer
0: Disable
1~20: 1 ~ 20 Sec
0
ASCII
mode
0: 7,N,2
1: 7,E,1
2: 7,O,1
3: 8,N,2
4: 8,E,1
5: 8,O,1
a
9-04 Communication
protocol
RTU
mode
6: 8,N,2
7: 8,E,1
8: 8,O,1
0