Installation and Operating Instructions - EOS Compact DC/HC
EN
Connecting the lines
Connecting the mains lead
1
Connect the cable for the mains connection to the four terminals
(MAINS)
L1
,
L2
,
L3
,
N
and
PE
.
The control unit is connected with a live current of 400 V 3 N AC 50 Hz
and fused separately with 3 x 16 A.
A 16 A cut-out with at least K characteristic must be used for fuse
protection.
As a rule, only a fixed connection may be connected to the mains
supply, whereby a configuration is provided that makes it possible to
separate the system from the mains supply with a contact opening
width of at least 3 mm (all poles).
3 4 N
N
V1 S1
L1 L2 L3 N
N
W V U N WB
WM FN F1 F2 LN LL
M A I N S
O V E N
V A P.
L S G
(PE)