Ensure the water supplies to both the hot and
cold inlets are isolated prior to commencing.
SEE IMAGE 31
STEP 1
Remove the faceplate bracket by
loosening the 4x M4 fixing screws and
carefully pulling the bracket off the
spout connector. SEE IMAGE 32
STEP 2
Remove the vertical temperature
adjustment gear, by unwinding its M5
fixing screw and levering it out of its
location on the back face of the box.
SEE IMAGES 33 &
34
STEP 3
Use an appropriate size spanner
or wrench, unwind the thermostatic
cartridge out of the mixer body. Lower
the cartridge down into the base of the
box until it is free of the mixer body.
SEE IMAGES 35, 36
& 37
STEP 4
Prior to discarding the cartridge,
remove the white plastic temperature
gear and the brass cartridge support
cover, and fit them onto the new
cartridge.
STEP 5
Lightly grease the new cartridge
o-rings and re-assemble by screwing
it into the mixer body until it reaches
a firm stop. Re-fit the temperature
gear and recommission the mixer as
detailed in Commissioning section on
page 19.
SERVICING THE THERMOSTATIC CARTRIDGE
Enware Product Code:
ATMS600
- Aquablend™ SQX™ Thermostatic Cartridge
ATMS649
- eSQX™ Temperature Control Gear