SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING THIS UNIT CALL
35
10
Electric Connections Accessories
Couple through eBus contact; all appliances equal air flow rate
Important:
Because of polarity sensitivity, always connect contacts X1-1 to X1-1 and contacts X1-2 to X1-2.
Never connect X1-1 and X1-2.
Connection RH (humidity)- sensor
For C2 (Slave2):
Set parameter 9 to 2 (= Slave 2).
Display always shows ventilation mode.
For C1 (Slave1):
Set parameter 9 to 1 (= Slave 1).
Display always shows ventilation mode.
For M (Master):
Set parameter 9 to 0 (= factory setting).
Display shows ventilation mode 1, 2 or 3.
A
= Multiple switch
B
= 2-pole connector
M
= (Master)
C1 t/m C*= (Slave); couple not more than 10 appliances
through Ebus
All units have the same air flow rates as the units set as “Master”.
Step
no.
Description
Factory
setting
Range
8
Communication
type
eBus
0t ( = Opentherm)
eBus
9
eBus address
0
0 = master
1- 9 = slave 1 - 9
A = energiSava 300/400
B = Control board
C = RH (humidity) - sensor
D = Cable supplied with RH sensor
E = Duct from dwelling
C1 = Brown
C2 = Blue
C3 = green/yellow
Step
no.
Description
Factory
setting
Range
30
Activating
RH-sensor
OFF
OFF = not active
ON = active
31
Sensitivity
0
+2most sensitive
+1
→
0 default setting RH-sensor
-1
→
-2least sensitive