Setting Values
STEP
NO.
DESCRIPTION
FACTORY
SETTING
ADJUSTING RANGE
STEP DISPLAY TEXT
+ SYMBOLS
1
Air flow rate mode Exc. 300 : mode
50 m
3
/h
0 m
3
/h of 50 m
3
/h
Air flow rate mode Exc. 400 : mode
50 m
3
/h
0 m
3
/h of 50 m
3
/h
2
Air flow rate mode Exc. 300 : mode 1
100 m
3
/h
50 m
3
/h - 300 m
3
/h
5 m
3
/h
1
Air flow rate mode Exc. 400 : mode 1
100 m
3
/h
50 m
3
/h - 400 m
3
/h
3
Air flow rate mode Exc. 300 : mode 2
150 m
3
/h
50 m
3
/h - 300 m
3
/h
5 m
3
/h
2
Air flow rate mode Exc. 400 : mode 2
200 m
3
/h
50 m
3
/h - 400 m
3
/h
4
Air flow rate mode Exc. 300 : mode 3
225 m
3
/h
50 m
3
/h - 300 m
3
/h
5 m
3
/h
3
Air flow rate mode Exc. 400 : mode 3
300 m
3
/h
50 m
3
/h - 400 m
3
/h
5
Bypass temperature
22,0 °C
15,0 °C - 35,0 °C
0,5 °C
BYPASS
6
Bypass hysteresis
2,0 °C
0,0 °C - 5,0 °C
0,5 °C
BY HYS
7
Operation bypass valve
0
0 (= Automatic)
1 (= Bypass valve closed)
2 (= Bypass valve open)
BYPASS
8
Communication
eBUS
Ot ( = Opentherm) eBUS
OT/BUS
9
Bus address
0
0 - 9 (0 = Master)
BUSADR
10
Central h heat recovery
OFF
OFF (= Central heat rec. off)
ON (= Central heat rec. on)
CV+WTW
11
Imbalance permissible
ON
OFF (= flow rate sup. equals extract)
ON (= imbalance permissible)
12
Fixed imbalance
0 m
3
/h
-100 m
3
/h t/m 100 m
3
/h
STEP
NO.
DESCRIPTION
FACTORY
SETTING
excl. Plus
ADJUSTING RANGE
STEP DISPLAY TEXT
+ SYMBOLS
13
Heater
0
0 (= no additional heater)
1 (= additional preheater)
2 (= postheater)
HEATER
14
Temperature postheater
21,0 °C
15,0 °C t/m 30,0 °C
0,5 °C
HEATER
15
Selection input 1
OFF
0 (= normally open contact)
1 (= 0 - 10V input)
2 (= normally closed contact)
3 (= input 1/ bypass open
→
12V;
bypass closed
→
0V)
4 (= input 1/ bypass open
→
0V;
bypass closed
→
12V)
V1
16
Minimum voltage input 1
0,0 V
0 Volt - 10 Volt
0,5 V
V1 MIN
17
Maximum voltage input 1
10,0 V
0 Volt - 10 Volt
0,5 V
V1 MAX
18
Conditions
switching input 1
0
0 (off)
1 (on)
2 (= On if conditions bypass open satisfied)
3 (= Bypass control)
4 (= Bedroom valve)
CN1
19
Supply fan mode
switching input 1
5
0 (= Input fan off)
1 (= Absolute min. flow rate 50m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch
6 (= Maximum flow rate)
7 (= no fan activation)
CN1