TO TEST VALVE PRESSURES (INPUT RATES):
The pressure taps are located on the front side of the valve (see Figure 33).
1. Using a long flat bladed screwdriver, turn set screw counter-clockwise to loosen.
2. Place
5
/
16
in (8 mm) I.D. hose over the pressure taps.
3. Check pressures using a manometer.
4. When finished, remove hose and tighten set screw.
Always check for gas leaks with a soap and water solution after completing the required
pressure test.
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
28
Initial Installation
QUALIFIED INSTALLERS ONLY
1
2
3
I
tem
n
umber
D
escrIptIon
1
Pilot Adjustment
Screw
2
Inlet Pressure Test
Point
3
Outlet Pressure Test
Point
Figure 33: Valve Details.
Table 6: Valve Details.