Basic Operation
Entek IRD 6687 Protection Monitor
7
Status Messages
The 6687 can display a number of status messages that alert you to alarms or to problems
with the transducers or monitoring system.
Note: The monitor backlight turns on and remains on while any of these messages appears on the
screen. This helps alert you to an alarm or a problem condition.
For information on setting the transducer input range or the alarm settings, see
“Configuration” on page 12.
In addition, there is another message that can appear. This message replaces the normal
display.
z
“SYS FAIL” message - This indicates that the monitor is unable to read the
configuration information from its internal memory. See the manual on 6600 monitor
troubleshooting for diagnostic information.
This message appears when the transducer voltage signal goes out of the
specified range. The number indicates the channel with the transducer fault.
See the manual on 6600 monitor troubleshooting for diagnostic information.
This message appears when the position exceeds one of the Alert alarm
setpoints. The number indicates the channel that exceeded the Alert alarm
setpoint. The underline indicates that the channel was the “first-out” alarm
for this monitor (or series of monitors if interconnected).
This message appears when the position exceeds one of the Danger alarm
setpoints. The number indicates the channel that exceeded the Danger alarm
setpoint. The underline indicates that the channel was the “first-out” alarm
for this monitor (or series of monitors if interconnected).
This message appears when the Danger alarm relays are manually inhibited
with the INHIBIT option on the User menu (page 15).
This message appears when the Danger alarm relays are inhibited (set with
the STARTUP option on the DELAYS submenu, page 24).
T X FAIL
1
ALERT
1
DANGER
1
IN HIBI T
1 2
STARTUP
1 2