Modbus settings
Page 50
Modbus settings
Data
Data Orientation
Select:
Tank oriented (= data grouped by tank) or Data oriented
(= data grouped by entity)
Start address
Enter start address (default = 0)
Record interval
Enter the number of registers between tank records
(default = 0050 for the Plus/Prime)
Advanced
Always force Data output to Fail if validity indicates failure.
Select to force the modbus registers to FFFFF in case of invalid data.
If
not selected the last measured value will be stored
Upon Prime Plus comm.fail. Force data output to Fail
Select to force the modbus registers to FFFFF in case of invalid data.
If
not selected the last measured value will be stored
Содержание Ensite Pro
Страница 74: ...Help Page 74 Help Click on this icon for on line assistance ...
Страница 78: ...Notes Page 78 ...
Страница 79: ...Notes Instruction manual Ensite Pro Configuration Tool Page 79 ...