Configure CIU Prime
Instruction manual Ensite Pro Configuration Tool
Page 45
If ‘RS-232C’ is selected, while in reality RS-485 hardware is applied,
communication can not be established.
Note 1
When a field communication fail occurs it is possible to maintain last
valid scan data in the CIU Prime database during a configurable
amount of time. The communication fail delay mechanism is reset on
the reception of data. A field communication fail can be caused by:
- modem delays bad cabling
- no answer because of a re
- initializing gauge
Note 2
When a data fail occurs it is possible to maintain the last valid scan
data in the CIU Prime database during a configurable amount of
time. The data fail mechanism is reset on the reception of valid data.
A data fail can be caused by:
- re-initialization of a gauge
- 802/811 digitizer failure
CIU-GPU
BPM-GPU
- Stopbits
Select: 1 or 2
N.A.
- Parity
Select: Odd, Even or None
N.A.
-Turn-around delay
Enter reply waiting time in ms (default = 20 ms)
- Handshake
Select: Full or Half
N.A.
- Mode
Select: RS-232C or RS-485
Select: EN-BPM
- FieldPort time-out
Enter timeout in ms
Enter timeout in ms
(default = 200 ms)
(default = 75 ms)
- FieldPort sensitivity
N.A.
Enter sensitivity (default = 7)
- FieldPort retries
Enter number of retries (default = 3)
-Communication fail delay Enter a time between 0 and 255 seconds
See note 1
- Data fail delay
Enter a time between 0 and 255 seconds
See note 2
= Enabled
Check to enable
N.A.