The Critical Component
EN Series User Manual
15
5. Use the default initial login indicated below. Note that the username and password are both case sensitive:
•
Username: admin
•
Password: 12345678
6. The ENLOGIC> prompt appears after you have logged in.
7. To configure network settings, enter the appropriate net commands and press Enter. All commands are case
sensitive. You can type ? to access the commands.
•
For the IPv4 DHCP configuration, configure this parameter.
•
net tcpip dhcp
•
Enter Y to validate and reboot the network management card.
•
For the static IPv4 configuration, configure these parameters.
•
net tcpip static x.x.x.x (ipaddress) x.x.x.x (netmask) x.x.x.x (gateway) Example: net tcpip static
192.168.1.100 255.255.255.0 192.168.1.1
•
Enter Y to validate and reboot the network management card.
Creating a Unique Pinout Connection
To create your own pinout connection for the RJ45 to Serial cable, make the wired connections as shown:
Pin
Description
Pin
1
1
2
RS232 RX
2
3
RS232 TX
3
4
4
5
Ground
5
6
6
7
7
8
8
Refer to the Web UI section and Using the Command Line Interface section of this manual for more information
about managing the PDU.
Connecting Environmental Sensors
(Optional)
To enable the EN Series device to detect Enlogic environmental conditions, connect one or more environmental sensors to the
PDU sensor port 1 or 2. The maximum distance for sensor cabling plugged into the device’s sensor port should not exceed 100
feet (30 m). The maximum number of sensor detection points should not exceed 6. Refer to the table below to determine how
many sensor detection points each sensor usess. For example, if using the 3 Tempe 1 Humidity sensor (EA9105), 4 sensor
points are in use, so only 2 additional sensor points are available.
Sensor Description
Number of
Sensor Points
ENLOGIC SKU
Alarm Beacon
1
EA9101
Temperature Sensor
1
EA9102
Temperature and Humidity Sensor
2
EA9103
(3) Tempe (1) Humidity Sensor
4
EA9105
Sensor Input Hub (3 sensor inputs)
n/a
EA9106
Door switch sensor
1
EA9109
Dry Contact Cable
1
EA9110
Spot Fluid Leak Sensor
1
EA9111
Rope Fluid Leak Sensor
1
EA9112
Smoke Sensor
1
EA9116
For more information about Enlogic’s environmental sensors, refer to the Installation sheet, included with each sensor.
1
8
CONN 1
CONN 2
1
5
6
9