CCS3100
35
User Manual R0.2
Method 2 Slope:
Considering the current pressure decrease rate and the times counted for the compressor to switch
to load, the new switch to load pressure value is calculated.
P164 Parameter Saving (Parameter Save)
Used to save device parameters and recall saved parameters.
No:
no actions
Save:
Backs up the current state of the parameters.
Use:
Restores the parameters that were saved with the backup command.
P166 Language Selection (Language)
Sets the language of the device. The device has Turkish and English languages in standard. When selected as user
defined, the third language installed via USB is activated. See “Application note
user defined third Language”
P167 Factory Settings (Return Factory)
There are 2 different restore factory settings options on the device. These are the built-in values in the device are the
user-defined factory values that can be loaded via USB-
MSC. See “
Application Note Loading Defined Parameters
Function”.
P168 Alarm History Reset (ClearFaultRecord)
With this parameter, all fault logs in the device are deleted.
P169 Motor Operation Time Reset (Motor Time Clear)
The motor running and running on load times in the device are reset with this parameter.
P170 Menu Timeout Duration (Menu Logout Time)
If no button is pressed for the time specified by this parameter during the time the device stays in the menu, the
syste
m automatically exits from the menu. In addition, if no logout is made with “P171 Menu Logout” parameter
after logging in for the menu, the menu can be accessed without password within the specified time.
P171 Menu Logout (Menu Logout)
Provides manual exit from the menu. Thus, it will be necessary to enter password on next menu login.