CCS3100
26
User Manual R0.2
P034: Screw Pressure Fail Alarm Delay (ScrewPress Alarm):
The expected delay time for screw pressure alarm and warning errors.
P035: Pressure Difference Fail Alarm Delay (DeltaPress Alarm):
The expected delay time for pressure difference alarm and warning errors.
P036: Fan Maximum Operation Time (Fan Working Time):
If the compressor stops while the fan running condition continues, the fan continues to run within this period. At the
end of the period, the fan is stopped regardless of the temperature conditions.
P037: Dryer Operation Time (Dryer Duration):
The duration of the dryer function. See “7.10 Application note Dryer Functions,”
P038: Pressure Difference Alarm Delay Time (Sufficiency):
The delay time for the qualification pressure error set with the "P013 Sufficiency Pressure" parameter.
P039: Horn Duration (Horn Duration):
Indicates the blowing time of the horn when an alarm occurs. At the end of this period, the horn is silenced.
2.2.3 Digital Input Parameters
Functions That Can Be Assigned to Inputs:
The functions that can be assigned to the inputs and their explanations are as follows.
None:
No function is assigned to the related digital input. If no connection has been made, it is recommended to set
it as "None".
EmerStp:
Emergency stop input. When this function is assigned and the input is active, the compressor is
unconditionally stopped.
Seperat.:
This is separator filter blocked sensor input. When this function is assigned and the input is active, the
compressor is unconditionally stopped.
OilPres.:
This is the oil pressure error input. When this function is assigned and the input is active, the compressor is
unconditionally stopped.
PhaseSeq:
This is the externally connected phase sequence relay error input.
When this function is assigned and the
input is active, the compressor is unconditionally stopped.
MThermic:
This is the error input for the motor thermic protection relay. When this function is assigned and the
input is active, the compressor is unconditionally stopped.
FThermic:
This is the error input for the fan thermic protection relay. When this function is assigned and the input is
active, the compressor is unconditionally stopped.
RemoteSS:
This is the remote start input. See "Application note Remote
start”.
StartBtn:
This is the function used to control the compressor from a remote point with the start button. When this
function is assigned and the input is active, the device confirms that the start button was pressed.
StopBtn:
This is the function used to control the compressor from a remote point with the stop button. When this
function is assigned and the input is active, the device confirms that the start button was pressed.
RemoteLD:
Used to control the load valve remotely. See "Application note Remote
start”.
PTC:
This function works only on DI7 input. When this function is assigned to the relevant input, the Motor PTC must
be connected to DI7 input as in the diagram below.