CCS3100
12
User Manual R0.2
Possible Causes and required actions:
The screw pressure sensor connected to the relevant terminal may be
defective or there may be a problem in the cable connections.
Temperature Sensor 1 Error (Temperatr1 Alarm)
Fault Definition:
Indicates a problem in the connection of screw temperature sensor that is connected to the
terminals 7-8 of the device, which are defined as AN2. It is a malfunction that stops the compressor rapidly.
Possible Causes and required actions:
The screw temperature sensor connected to the relevant terminal may be
defective or there may be a problem in the cable connections.
Temperature Sensor 2 Error (Temperatr2 Alarm)
Fault Definition:
Indicates a problem in the connection of second temperature sensor that is connected to the
terminals 3-4 of the device, which are defined as AN4. It is a malfunction that stops the compressor rapidly.
Possible Causes and required actions:
The second temperature sensor connected to the relevant terminal may be
defective or there may be a problem in the cable connections.
Line Pressure Warning (Line Press Warning)
Warning Definition:
Indicates that the value read by the line pressure sensor is above the value entered to the "P005
Line Warning Value" parameter. It is just a warning message. Does not stop the motor.
Possible Causes and required actions:
Make sure that the relevant parameter is suitable for your application.
Line Pressure Alarm (Line Alarm)
Fault Definition:
Indicates that the value read by the line pressure sensor is above the value entered to the "P004
Line Alarm Value " parameter. It is a malfunction that stops the compressor rapidly.
Possible Causes and required actions:
Make sure that the relevant parameter is suitable for your application.
Screw Pressure Warning (Screw Press Warn)
Warning Definition:
Indicates that the value read by the screw pressure sensor is above the value entered to the
"P009 Screw Pressure Warning" parameter. It is just a warning message. Does not stop the motor.
Possible Causes and required actions:
Make sure that the relevant parameter is suitable for your application.
Screw Pressure Alarm (ScrewPress Alarm)