CCS3100
32
User Manual R0.2
P126 Preheat Temperature Limit (Preheat Limit)
If the temperature measured by the screw temperature sensor connected to terminals 7-8 of the device, which are
defined as AN2, at the first start-up, is less than the value entered to this parameter, the device runs in preheating
mode until the temperature exceeds this value. See "Application note Preheat"
P127 Temperature-1 Sensor Type Select (Temp1 SensorType)
Type of the screw temperature sensor connected to terminals 7-8 of the device, which are defined as AN2, is
determined by this parameter.
P128 Temperature Unit (Temperature Unit)
The temperature measurement unit used by the device in display and control stages is set with this parameter.
P129 Fan Start Temperature Level (Fan Start)
If the function of one of the outputs of the device is set as "Fan", when the value measured by the screw
temperature sensor connected to terminals 7-8, which are defined as AN2, is more than the value entered with this
parameter, the relevant Fan output is activated until it reaches the stop temperature.
P130 Fan Stop Temperature Level (Fan Stop)
If the function of one of the outputs of the device is set
as “Fan”, when the value measured by the screw
temperature sensor connected to terminals 7-8, which are defined as AN2, is less than the value entered with this
parameter, the relevant Fan output is deactivated until it reaches the running temperature.
P131 Dryer Start Temperature Level (Dryer Start)
For parameter description see "Application Note Dryer Functions"
P132 Dryer Stop Temperature Level (Dryer Stop)
For parameter description see "Application Note Dryer Functions"
P134 Temperature-2 High-Fail Alarm (Temp2 High Alarm)
When the temperature measured by the second temperature sensor connected to the terminals 3-4 of the device,
which are defined as AN4, exceeds the value entered to this parameter, the device gives a “
Temp2Upper Alarm
”.
P135 Temperature-2 High-Warning Alarm (Temp2 High Warn)
When the temperature measured by the second temperature sensor connected to the terminals 3-4 of the device,
which are defined as AN4, exceeds the value entered to this parameter, the device gives a “
Temp2 Upper Warn
”.
P136 Temperature-2 Low-Fail Alarm (Temp2 Low Alarm)
When the temperature measured by the screw temperature sensor connected to the terminals 3-4 of the device,
which are defined as AN4, drops below the value entered to this parameter, the device gives a " Temp2 Down Alarm"
and stops the compressor.
P137 Temperature-2 Low-Warning Alarm (Temp2 Low Warn)
When the temperature measured by the screw temperature sensor connected to the terminals 3-4 of the device,
which are defined as AN4, drops
below the value entered to this parameter, the device gives a “
Temp2 Down Warn
”.
P138 Temperature-2 Sensor Type Select (Temp2 SensorType)
The type of the second temperature sensor connected to the terminals 3-4, which are defined as AN4, is determined
by this parameter.
P139 Temperature-2 Sensor Operation Mode (Temp2 SensorMode)
The operating mode of the second temperature sensor connected to the terminals 3-4, which are defined as AN4 of
the device, is determined by this parameter. Explanations for 3 different options are as follows.
Off:
Should be in off mode when the second temperature sensor is not used.