CCS3100
16
User Manual R0.2
S Phase Voltage High Warning (Vs High Warn)
Warning Definition:
Indicates that the S Phase Voltage connected to t
he terminal “24”, which is defined as “S”, is
higher than the value entered to the “P146
Mains Voltage High Warn
” parameter. It is just a warning message. Does
not stop the motor.
Possible Causes and required actions:
There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
S Phase Voltage High Fault (Vs High Alarm)
Fault Definition:
Indicates that the S Phase Voltage connected to the terminal “24”, which is defined as “S”, is higher
than the value entered to the “P145
Mains Voltage High Alarm
” parameter. It is a malfunction that stops the
compressor rapidly.
Possible Causes and required actions:
There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
T Phase Voltage High Warning (Vt High Warn)
Warning Definition:
Indicates that the T Phase Voltage connected to the terminal “23”, which is defined as “T”, is
higher than the value entered to the “P146
Mains Voltage High Warn
” parameter. It is just a warning message. Does
not stop the motor.
Possible Causes and required actions:
There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
T Phase Voltage High Fault (Vt High Alarm)
Fault Definition:
Indicates that the T Phase Voltage connected to the terminal “23”, which is defined as “T”, is higher
than the value entered to the “P145
Mains Voltage High Alarm
” parameter. It is a malfunction that stops the
compressor rapidly.
Possible Causes and required actions:
There may be a voltage rise in the system. The value that is entered to the
parameter may have been wrong for the application.
R Phase Voltage Low Warning (Vr Low Warn)
Warning Definition:
Indicate
s that the R Phase Voltage connected to the terminal “25”, which is defined as “R”, is
lower than the value entered to the “
P144 Mains Voltage Low Warn
” parameter. It is just a warning message. Does
not stop the motor.