20
• AC output
Enfinity inverters are designed for single phase grid. The Voltage range is from 180V to 260V (200V-270V
for Australia), frequency is 47Hz~52Hz/57Hz~61.5Hz. Other technical requests should comply with the
requirement of local public grid.
Enfinity model
1000TL
1650TL
2200TL
2800TL
3300TL
3680TL
4400TL
5000TL
Cable
4mm
2
Micro-Breaker
16A
16A
20A
20A
20A
25A
25A
25A
Distance
max. 15m
Micro-breaker should be installed between inverter and grid, and its leakage current needs to be >30mA.
Any load should not be connected with the inverter directly.
Figure 17:
incorrect connections between load and inverter
Impedance of the Enfinity inverter AC connecting dot should be less than 2
Ω
. To ensure reliable anti-
islanding function , PV cable should be used to ensure wire loss < 1% of normal power.
This product has a professional IP66 AC waterproof connector. You have to wire AC by yourself. Please
see figure 18 and 19 for AC connector disassembling guide.