Accessing Sinus H Inverter Parameters using the PROFInet Record Data Object
Using the PROFInet Record Data object, you can access the Sinus H inverter parameters for data
reading and writing, without the PROFIdrive communication protocol.
The inverter’s parameter data is assigned to the PROFInet Record Data from the index address
0h5000. Using the PROFInet IO RW service, you can directly access the addresses to perform
reading and writing.
For example, Siemens PLC users may access the inverter’s parameter data mapped to the PROFInet
Record using “WRREC” and “RDREC” function blocks. Refer to the user’s manual that that is supplied
with the inverter for more information about the inverter parameter data.
E.g.) The inverter’s common parameter address 0h0001 is assigned to a PROFInet index address
0h5001.