SINUS H
PROFInet Module
20
/
34
7
Supported PROFIdrive Cyclic Telegram
The Sinus H communication module supports “Standard” and “Vendor Specific” telegrams. On a
PROFInet network, it can exchange cyclic telegrams with a PLC, at a minimum cycle time of 8 ms.
Each telegram is expressed as a submodule in PROFInet network communication, and can be
assigned to either Slot1 or Subslot 2 at the communication module.
7.1
Standard Telegram (Mode : 0)
Standard telegram1
Byte 1-2
Byte 3-4
PLC to Sinus H
Control word (STW1)
Setpoint value
Sinus H to PLC
Status word (ZSW1)
Actual speed value
7.2
Vendor Specific Telegram (Mode : 1)
Vendor Specific
telegram1
Byte 1-2
Byte 3-4
Byte 5-6
Byte 7-8
Byte 9-10
PLC to Sinus H
Control
word
(STW1)
Setpoint
value
Dummy
Dummy
Dummy
Sinus H to PLC
Status word
(ZSW1)
Actual
speed value
Alarm Info
Torque
Current
The following table lists settings for Standard and Vendor Specific Telegrams.
7.2.1
Control word (STW1)
Bit
Name
Value Description
0
ON
1
Ready for operation
(Operation by a PLC is available.)
OFF1
0
NOT Ready for operation
(Operation by a PLC is not available.)
1
No OFF2
1
OFF2 (Coast Stop) feature is disabled. Current operation is
maintained.
OFF2 (Coast Stop)
0
Stops the motor using a free-run stop (emergency stop).
2
No OFF3
1
OFF3 (Quick Stop) feature is disabled. Current operation is
maintained.
OFF3 (Quick Stop)
0
Stops the motor using the setting at Sinus H inverter (ADV-8
“Stop Mode”).
3
Enable Operation
1
Operates the motor using the Setpoint value (frequency
reference received from a PLC via the PROFInet network
communication.
Disable Operation
0
Stops the motor using the setting at Sinus H inverter (ADV-8
“Stop Mode”).
4
Enable Ramp
Generator
1
Performs acceleration and deceleration based on the
acceleration and deceleration time settings at Sinus H
inverter (PAR->DRV) to reach the Setpoint (frequency