PROFInet Module
SINUS H
19
/
34
Status transitions are directed by the commands that are periodically transmitted from the PLC, and
the command types are as follows. Refer to
for more information.
•
NoQuickStop Command
•
NoCoastStop Command
•
SwitchOFF Command
•
SwitchON Command
•
OperationEnable Command
•
OperationDisable Command
•
QuickStop Command
•
CoastStop Command
The following table lists status transition events and the inverter operations:
Source Status
Target Status
Event
Action (Inverter operation)
“Switch On
Inhibited”
“Ready For
Switching On”
"SwitchOFF"
and "NoQuickStop"
and "NoCoastStop"
None (Motor is stopped.)
“Ready For
Switching On”
“Switch On
Inhibited”
"QuickStop"
or
"CoastStop"
None (Motor is stopped.)
“Ready For
Switching On”
“Ready For
Operation”
"SwitchON"
None (Motor is stopped.)
“Ready For
Operation”
“Ready For
Switching On”
"SwitchOFF"
None (Motor is stopped.)
“Ready For
Operation”
“Operation”
"OperationEnable"
Motor is run.
“Operation”
“Ready For
Operation”
"OperationDisable"
Motor is stopped (the Sinus H
inverter stops the motor according
to the ADV-8 “Stop Mode”
settings).
“Operation”
“Switch On
Inhibited”
"CoastStop"
Motor is stopped (Free Run Stop).
“Operation”
“Switch On
Inhibited”
"QuickStop"
Motor is stopped (the Sinus H
inverter stops the motor according
to the ADV-8 “Stop Mode”
settings).