Chapter V Maintenance
5.1 Daily Inspection and Maintenance
Affected by environment temperature, humidity, vibration, and inverter internal component
aging, the inverter may suffer some potential problems during operation. In order to stably operate
the inverter for a long term, conduct periodical inspection once each year.
5.1.1 Requirements of Inspection and Maintenance
1. The inspection shall be conducted by professional technician. When necessary, cut off the
power supply of inverter.
2. Avoid leaving metal components and parts in inverter, or else it may damage the equipment.
3. The inverter has conducted electrical insulation experiment before leaving factory, so the
user needn’t conduct high-voltage insulation test.
4. If you intend to conduct insulation test on inverter, all input and output terminals must be
short circuit reliably. It is forbidden to conduct insulation test on single terminate. Please
use 500V megameter during test.
5. It is forbidden to use megameter to measure control loop.
6. When conducting insulation test on motor, remove the connecting line between motor and
inverter.
5.1.2 Key Points of Inspection and Maintenance
Please use the inverter under the environment recommended in the manual and conduct
inspection and maintenance according to the following table.
Inspection Frequency
Inspection Item
Inspection Content
Judgment Standard
Daily
Periodically
√
Operating
Environment
1.Temperature and
humidity
2. Dust and gas
1. Temperature <50°C
2. Humidity <90%, without moisture
condensation
3. No peculiar smell. No combustible or
explosive gas
√
Cooling System
1. Installation
environment
2. Radiator
1. The ventilation of installation
environment is good
2. The air flue of radiator is not blocked
√
Inverter Body
1. Vibration, temperature
rise
2. Noise
3. Wire, terminal
1. Vibration is stable and shell
temperature rise is normal
2. No abnormal noise or peculiar smell
3. Tighten the screw
√
Motor
1. Vibration, temperature
rise
2. Noise
1. Operate stably. Temperature is normal.
2. No abnormal noise
√
Input and Output
Parameter
1. Input Voltage
2. Output Current
1. Input voltage is in specified scope
2. Output current is under rated value