Operation Instruction of BS Series Solar Pumping Inverter
Operation Control
33
Chapter IV: Failure Diagnosis
4.1 Explanation and Solution for Fault Code
BS series solar pumping inverter has complete protection. When system suffers failure, the
inverter will take protective measures: the general protective measures are to stop the output of
drive signal of motor and forbid to re-start within a certain period.
When failure or protection happens, the failure or protection needs to reset the inverter. Power
off input power supply, then power on it. If the failure is not still settled, please contact with
manufacturer to settle it.
The common failures are listed as follows:
Code
Code Description
Possible Reasons
Countermeasures
Power off
No failure
Inc over Volt
Dec over Volt
Con over Volt
Overvoltage
Input voltage is too
high
Check the voltage of solar
array
Vbus low
Undervoltage
Input voltage is too
low
Illumination
intensity
is
too
weak
Check the voltage of solar
array
In cover Current
Dec over Current
con over Current
Overcurrent
The load of water
pump is too large
The voltage of cell
array is too low
The motor wiring
is too long
Replace small-power water
pump load
Check the voltage of solar
array
Shorten the wiring between
inverter and motor
Overload Tel
Water pump is
overload
Load is too large
Decrease maximum operation
frequency